The binary input controlling the function is defined in ACT or SMT. The CHNGLCK function is
configured using ACT.
LOCK
Binary input signal that will activate/deactivate the function, defined in ACT or SMT.
ACTIVE
Output status signal
OVERRIDE
Set if function is overridden
GUID-8C333BC0-AA7A-4ED1-A772-18C22E8EEE62 v4
When CHNGLCK has a logical one on its input, then all attempts to modify the IED configuration
and setting will be denied and the message "Error: Changes blocked" will be displayed on the local
HMI; in PCM600 the message will be "Operation denied by active ChangeLock". The CHNGLCK
function should be configured so that it is controlled by a signal from a binary input card. This
guarantees that by setting that signal to a logical zero, CHNGLCK is deactivated. If any logic is
included in the signal path to the CHNGLCK input, that logic must be designed so that it cannot
permanently issue a logical one to the CHNGLCK input. If such a situation would occur in spite of
these precautions, then please contact the local ABB representative for remedial action.
15.5.3
Setting guidelines
GUID-D805FDEE-AEA7-46F5-9358-E68C4C6C6DA7 v2
The Change lock function CHNGLCK does not have any parameters available in the local HMI or
PCM600.
15.6
IED identifiers TERMINALID
15.6.1
Identification
GUID-CEB88FE4-C94A-41DE-BA72-95322C31CA90 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED identifiers
TERMINALID
-
-
15.6.2
Application
IP15057-1 v1
15.6.2.1
Customer specific settings
M11789-48 v5
The customer specific settings are used to give the IED a unique name and address. The settings
are used by a central control system to communicate with the IED. The customer specific
identifiers are found in the local HMI under Configuration/Power system/Identifiers/
TERMINALID
The settings can also be made from PCM600. For more information about the available identifiers,
see the technical manual.
Use only characters A - Z, a - z and 0 - 9 in station, unit and object names.
1MRK 505 287-UUS B
Section 15
Basic IED functions
Busbar protection REB650
229
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...