Where:
1)
shows how to connect the secondary side of open delta VT to one VT input in
the IED.
+3Vo shall be connected to the IED.
2)
is TRM where this voltage input is located. It shall be noted that for this voltage
input the following setting values shall be entered:
138
3
138
3
VTprim
kV
=
×
=
EQUATION1928 V1 EN-US
(Equation 5)
115
sec
3
115
3
VT
V
=
×
=
EQUATION1929 V1 EN-US
(Equation 6)
Inside the IED, only the ratio of these two parameters is used. It shall be noted
that the ratio of the entered values exactly corresponds to ratio of one
individual open delta VT.
138
138
3
115
115
3
=
EQUATION1930 V1 EN-US
(Equation 7)
4)
shows the connection made in Signal Matrix Tool (SMT), which connect this
voltage input to the fourth input channel of the preprocessing function block 4).
5)
preprocessing block has a task to digitally filter the connected analog inputs
and calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental
frequency phasors for the first three input channels (channel one taken as
reference for sequence quantities)
These calculated values are then available for all built-in protection and control
functions within the IED, which are connected to this preprocessing function
block in the configuration tool. For this application most of the preprocessing
settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically
required only for IEDs installed in the generating stations) then the setting
parameters
DFTReference shall be set accordingly.
1MRK 505 287-UUS B
Section 4
Analog inputs
Busbar protection REB650
49
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...