Name
Type
Default
Description
COUNTER5
BOOLEAN
0
Input for counter 5
COUNTER6
BOOLEAN
0
Input for counter 6
RESET
BOOLEAN
0
Reset of function
Table 264:
CNTGGIO Output signals
Name
Type
Description
VALUE1
INTEGER
Output of counter 1
VALUE2
INTEGER
Output of counter 2
VALUE3
INTEGER
Output of counter 3
VALUE4
INTEGER
Output of counter 4
VALUE5
INTEGER
Output of counter 5
VALUE6
INTEGER
Output of counter 6
12.2.5
Settings
Table 265:
CNTGGIO Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
12.2.6
Monitored data
Table 266:
CNTGGIO Monitored data
Name
Type
Values (Range)
Unit
Description
VALUE1
INTEGER
-
-
Output of counter 1
VALUE2
INTEGER
-
-
Output of counter 2
VALUE3
INTEGER
-
-
Output of counter 3
VALUE4
INTEGER
-
-
Output of counter 4
VALUE5
INTEGER
-
-
Output of counter 5
VALUE6
INTEGER
-
-
Output of counter 6
12.2.7
Operation principle
Event counter (CNTGGIO) has six counter inputs. CNTGGIO stores how many times
each of the inputs has been activated. The counter memory for each of the six inputs
is updated, giving the total number of times the input has been activated, as soon as an
input is activated.
To not risk that the flash memory is worn out due to too many writings, a mechanism
for limiting the number of writings per time period is included in the product. This
Section 12
1MRK 505 288-UEN A
Monitoring
342
Technical manual
Summary of Contents for Relion 650 Series REB650
Page 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 84: ...78 ...
Page 152: ...146 ...
Page 278: ...272 ...
Page 316: ...310 ...
Page 432: ...426 ...
Page 504: ...498 ...
Page 518: ...512 ...
Page 566: ...560 ...
Page 567: ...561 ...