Name
Values (Range)
Unit
Step
Default
Description
Latched7
Pulsed
Latched
-
-
Pulsed
Setting for pulsed/latched mode for output
7
tPulse7
0.01 - 6000.00
s
0.01
0.10
Output 7 Pulse Time
Latched8
Pulsed
Latched
-
-
Pulsed
Setting for pulsed/latched mode for output
8
tPulse8
0.01 - 6000.00
s
0.01
0.10
Output 8 pulse time
10.7.6
Operation principle
The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the
eight outputs is activated based on the command sent from the operator place selected.
The settings
Latchedx
and
tPulsex
(where x is the respective output) will determine if
the signal will be pulsed (and how long the pulse is) or latched (steady). BLOCK will
block the operation of the function – in case a command is sent, no output will be
activated.
PSTO is the universal operator place selector for all control functions.
Although, PSTO can be configured to use LOCAL or ALL operator
places only, REMOTE operator place is used in SPC8GGIO function.
10.8
Automation bits AUTOBITS
10.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
AutomationBits, command function for
DNP3
AUTOBITS
-
-
10.8.2
Functionality
The Automation bits function AUTOBITS is used to configure the DNP3 protocol
command handling. Each of the 3 AUTOBITS available has 32 individual outputs
available, each can be mapped as a binary output point in DNP3.
1MRK 505 288-UEN A
Section 10
Control
263
Technical manual
Summary of Contents for Relion 650 Series REB650
Page 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 84: ...78 ...
Page 152: ...146 ...
Page 278: ...272 ...
Page 316: ...310 ...
Page 432: ...426 ...
Page 504: ...498 ...
Page 518: ...512 ...
Page 566: ...560 ...
Page 567: ...561 ...