Function
Range or value
Accuracy
Definite time delay,
step 1
(0.00 - 6000.00) s
± 0.5% ± 25 ms
Definite time delays,
step 2
(0.000-60.000) s
± 0.5% ±25 ms
Minimum operate
time, inverse
characteristics
(0.000–60.000) s
± 0.5% ± 25 ms
Operate time, start
function
30 ms typically at 1.2 to 0.5U
set
-
Reset time, start
function
40 ms typically at 0.5 to 1.2 xU
set
-
Critical impulse time
10 ms typically at 1.2 to 0.8 x U
set
-
Impulse margin time
15 ms typically
-
8.2
Two step overvoltage protection OV2PTOV
8.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Two step overvoltage protection
OV2PTOV
3U>
SYMBOL-C-2U-SMALLER-THAN
V2 EN
59
8.2.2
Functionality
Overvoltages may occur in the power system during abnormal conditions such as
sudden power loss, tap changer regulating failures, and open line ends on long lines.
Two step overvoltage protection (OV2PTOV) function can be used to detect open line
ends, normally then combined with a directional reactive over-power function to
supervise the system voltage. When triggered, the function will cause an alarm, switch
in reactors, or switch out capacitor banks.
OV2PTOV has two voltage steps, where step 1 can be set as inverse or definite time
delayed. Step 2 is always definite time delayed.
OV2PTOV has a high reset ratio to allow settings close to system service voltage.
1MRK 505 288-UEN A
Section 8
Voltage protection
133
Technical manual
Summary of Contents for Relion 650 Series REB650
Page 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 84: ...78 ...
Page 152: ...146 ...
Page 278: ...272 ...
Page 316: ...310 ...
Page 432: ...426 ...
Page 504: ...498 ...
Page 518: ...512 ...
Page 566: ...560 ...
Page 567: ...561 ...