17.3
Energizing inputs
Table 441:
TRM — Energizing quantities, rated values and limits for transformer inputs
Description
Value
Frequency
Rated frequency f
r
50 or 60 Hz
Operating range
f
r
± 10%
Current inputs
Rated current I
r
0.1 or 0.5 A
1)
1 or 5 A
2)
Operating range
0 – 50 A
0 – 500 A
Thermal withstand
100 A for 1 s
500 A for 1 s
*)
20 A for 10 s
100 A for 10 s
8 A for 1 min
40 A for 1 min
4 A continuously
20 A continuously
Dynamic withstand
250 A one half wave
1250 A one half wave
Burden
< 1 mVA at I
r
= 0.1 A
< 10 mVA at I
r
= 1 A
< 20 mVA at I
r
= 0.5 A
< 200 mVA at I
r
= 5 A
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Voltage inputs
**)
Rated voltage U
r
100 or 220 V
Operating range
0 – 420 V
Thermal withstand
450 V for 10 s
420 V continuously
Burden
< 50 mVA at 100 V
< 200 mVA at 220 V
**)
all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency
1) Residual current
2) Phase currents or residual current
17.4
Binary inputs
Table 442:
Binary inputs
Description
Value
Operating range
Maximum input voltage 300 V DC
Rated voltage
24...250 V DC
Current drain
1.6...1.8 mA
Power consumption/input
<0.38 W
Threshold voltage
15...221 V DC (parametrizable in the range in steps
of 1% of the rated voltage)
Section 17
1MRK 505 288-UEN A
Technical data
514
Technical manual
Summary of Contents for Relion 650 Series REB650
Page 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 84: ...78 ...
Page 152: ...146 ...
Page 278: ...272 ...
Page 316: ...310 ...
Page 432: ...426 ...
Page 504: ...498 ...
Page 518: ...512 ...
Page 566: ...560 ...
Page 567: ...561 ...