The interlocking module is connected to the surrounding functions within a bay as
shown in figure
Interlocking
modules in
other bays
Interlocking
module
SCILO
SCSWI
Apparatus control
modules
SXCBR
SCILO
SCSWI
SXSWI
Apparatus control
modules
SCILO
SCSWI
SXSWI
Apparatus control
modules
en04000526.vsd
IEC04000526 V1 EN
Figure 108:
Interlocking module on bay level
Bays communicate via the station bus and can convey information regarding the
following:
•
Unearthed busbars
•
Busbars connected together
•
Other bays connected to a busbar
•
Received data from other bays is valid
illustrates the data exchange principle.
Disc QB1 and QB2 closed
WA1 not earthed
WA2 not earthed
WA1 and WA2 interconn
Disc QB1 and QB2 closed
WA1 not earthed
WA2 not earthed
WA1 and WA2 interconn
. . .
. .
Station bus
QB1
WA1
WA2
Bay 1
Bay n
Bus coupler
WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn
WA1 and WA2 interconn
in other bay
QB2
QA1
QB9
QB1
QB2
QA1
QB9
QB2
QB1
QA1
QC1
QC2
en05000494.vsd
IEC05000494 V1 EN
Figure 109:
Data exchange between interlocking modules
Section 10
1MRK 505 288-UEN A
Control
252
Technical manual
Summary of Contents for Relion 650 Series REB650
Page 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 84: ...78 ...
Page 152: ...146 ...
Page 278: ...272 ...
Page 316: ...310 ...
Page 432: ...426 ...
Page 504: ...498 ...
Page 518: ...512 ...
Page 566: ...560 ...
Page 567: ...561 ...