IPOS1
IPOS2
Name of displayed string Default string value
0
0
PosUndefined
P00
1
0
Position1
P01
0
1
Position2
P10
1
1
PosBadState
P11
10.6
IEC 61850 generic communication I/O functions
DPGGIO
10.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
DPGGIO
-
-
10.6.2
Functionality
The IEC 61850 generic communication I/O functions DPGGIO function block is used
to send double indications to other systems or equipment in the substation using
IEC61850. It is especially used in the interlocking and reservation station-wide logics.
10.6.3
Function block
DPGGIO
OPEN
CLOSE
VALID
POSITION
IEC09000075_1_en.vsd
IEC09000075 V1 EN
Figure 111:
DPGGIO function block
10.6.4
Signals
Table 157:
DPGGIO Input signals
Name
Type
Default
Description
OPEN
BOOLEAN
0
Open indication
CLOSE
BOOLEAN
0
Close indication
VALID
BOOLEAN
0
Valid indication
Table 158:
DPGGIO Output signals
Name
Type
Description
POSITION
INTEGER
Double point indication
Section 10
1MRK 505 288-UEN A
Control
260
Technical manual
Summary of Contents for Relion 650 Series REB650
Page 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 84: ...78 ...
Page 152: ...146 ...
Page 278: ...272 ...
Page 316: ...310 ...
Page 432: ...426 ...
Page 504: ...498 ...
Page 518: ...512 ...
Page 566: ...560 ...
Page 567: ...561 ...