10.2.2.3
Function block
SCSWI
BLOCK
PSTO
L_SEL
L_OPEN
L_CLOSE
AU_OPEN
AU_CLOSE
BL_CMD
RES_EXT
SY_INPRO
SYNC_OK
EN_OPEN
EN_CLOSE
XPOS*
EXE_OP
EXE_CL
SELECTED
START_SY
POSITION
OPENPOS
CLOSEPOS
CMD_BLK
L_CAUSE
POS_INTR
XOUT
IEC09000087_1_en.vsd
IEC09000087 V1 EN
Figure 75:
SCSWI function block
10.2.2.4
Signals
Table 101:
SCSWI Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PSTO
INTEGER
2
Operator place selection
L_SEL
BOOLEAN
0
Select signal from local panel
L_OPEN
BOOLEAN
0
Open signal from local panel
L_CLOSE
BOOLEAN
0
Close signal from local panel
AU_OPEN
BOOLEAN
0
Used for local automation function
AU_CLOSE
BOOLEAN
0
Used for local automation function
BL_CMD
BOOLEAN
0
Steady signal for block of the command
RES_EXT
BOOLEAN
0
Reservation is made externally
SY_INPRO
BOOLEAN
0
Synchronizing function in progress
SYNC_OK
BOOLEAN
0
Closing is permitted at set to true by the
synchrocheck
EN_OPEN
BOOLEAN
0
Enables open operation
EN_CLOSE
BOOLEAN
0
Enables close operation
XPOS
GROUP
SIGNAL
-
Group signal from XCBR/XSWI
Table 102:
SCSWI Output signals
Name
Type
Description
EXE_OP
BOOLEAN
Execute command for open direction
EXE_CL
BOOLEAN
Execute command for close direction
SELECTED
BOOLEAN
Select conditions are fulfilled
START_SY
BOOLEAN
Starts the synchronizing function
POSITION
INTEGER
Position indication
OPENPOS
BOOLEAN
Open position indication
Table continues on next page
1MRK 505 288-UEN A
Section 10
Control
179
Technical manual
Summary of Contents for Relion 650 Series REB650
Page 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 84: ...78 ...
Page 152: ...146 ...
Page 278: ...272 ...
Page 316: ...310 ...
Page 432: ...426 ...
Page 504: ...498 ...
Page 518: ...512 ...
Page 566: ...560 ...
Page 567: ...561 ...