6.3
Resetting IED
6.3.1
Clearing and acknowledging via the local HMI
All messages and indications, including LEDs and latched outputs as well as
registers and recordings can be reset, acknowledged or cleared with the Clear
button. Pressing the Clear button activates a menu for selecting the wanted
clearance or reset function. Events and alarms assigned to programmable LEDs can
also be cleared with the Clear button.
1.
Press
to activate the Clear view.
All the items that can be cleared are shown:
•
Indications and LEDs
•
Programmable LEDs
•
Recorded data
•
Events
•
Disturbance records
•
Temperature functions
•
Trip lockout functions
A070860 V3 EN
Figure 65:
Clear view
2.
Select the item to be cleared with
or
.
3.
Press
, change the value with
or
and press
again.
The item is now cleared.
4.
Repeat the steps to clear other items.
Use the
button as a shortcut for clearing. The first three-second
press clears the indications. The second three-second press clears
the programmable LEDs.
1MRS756708 C
Section 6
Operating procedures
615 series
81