Document all changes to parameter settings.
For more information, see PCM600 documentation.
8.5.3.3
Defining disturbance recorder channel settings
1.
Select
Main Menu/Configuration/Disturbance recorder/Channel settings
.
2.
Press
or
to scroll the view.
3.
To change channel settings, press
.
Each analog channel has an equal set of parameters and correspondingly, each
binary channel has an equal set of parameters.
8.5.3.4
Configuring analog inputs
1.
Select
Main Menu/Configuration/Analog inputs
and press
.
2.
Select the analog input to be configured with
or
.
3.
Press
, change the value with
or
and press
again.
•
For CTs, the secondary current and primary current need to be set to the
correct values.
•
For VTs, the secondary voltage and primary voltage need to be set to
the correct values.
8.6
Testing IED operation
The IED has to be in the test mode before the digital outputs and certain output
signals of protection and other functions can be activated.
8.6.1
Selecting the test mode
The test mode can be activated using the LHMI. The green Ready LED will be
flashing to indicate that the test mode is activated.
The Ready LED also flashes if the IED detects a diagnostic failure.
Check the test mode setting and the IED's IRF alarm contact status
to find the reason for the failure.
Section 8
1MRS756708 C
Commissioning
116