6
The following UL listed compression lugs may be used
Wire Size
ABB/ T&B
Burndy
Panduit
MAC
CU only
CU/ AL
CU only
CU/ AL
CU only
CU/ AL
CU only
CU/ AL
250 MCM
54275
60256
YA29-2LN
YA29A3
LCC250-12
LAB250-12
MSB250-8N
MLB250-8N
54868BE
YA29-2N
YA29AY-2N
MRB250-8N MULB250-8N
300 MCM
54280
60262
YA30-2LN
YA30A3
LCC300-12
LAB300-12
MSB300-8N
MLB300-8N
54870BE
YA30-2N
YA30AY-2N
MRB300-8N MULB300-8N
350 MCM
54282
60267
YA31-2LN
YA31A3
LCC350-12
LAB350-12
MSB350-8N
MLB350-8N
54872BE
YA31-2N
YA31AY-2N
MRB350-8N MULB350-8N
400 MCM
54874
60269
YA32-2LN
YA32A3
LCC400-12
LAB400-12
MSB400-8N
MLB400-8N
YA32-2N
YA32AY-2N
MRB400-8N MULB400-8N
500 MCM
54266
60273
YA34-2LN
YA34A3
LCC500-12
LAB500-12
MSB500-8N
MLB500-8N
54876BE
YA34-2N
YA34AY-2N
MRB500-8N MULB500-8N
600 MCM
54289
60275
YA36-2LN
YA36A3
LAB600-12
MSB600-8N
MLB600-8N
54878BE
YA36-2N
YA36AY-2N
MRB600-8N MULB600-8N
700 MCM
54291
60277
750 MCM
54223
YA39-2LN
LCC750-12
LAB750-12
MSB750-8N
54880BE
YA39-2N
MRB750-8N
Neutral bonding on main-modules
Neutral will not be bonded to the enclosure from the factory.
If you need to bond the neutral, use the bonding jumper
supplied with the unit. Unfasten from the factory-installed
position Rotate jumper and fasten to the neutral bus at torque
indicated on label in unit.Secure the jumper to the enclosure
with hardware provided at torque indicated on label in unit.
Breaker accessories
The following breaker accessories can be field-installed.
They are sold separately.
Lug-kit
Shunt-trip
Padlocking provision on main breaker
Catalogue Number
Application
Electrical System
Main Rating
RXT7LUGKIT750
120/240V or
208Y/120V
For use with any main
module with XT7 Frame
device 1000A and 1200A
MCB’s and 800A MFS. This
lug kit allows field
installation of larger lugs
that accommodate (3)
500-750kcmil AL/CU cables
per phase and neutral
Catalogue Number
Application
Electrical System
Main-Breaker rating
1SDA104934R1
120/240V
400A, 600A, 800A
1SDA073672R1
110/120V
1000A, 1200A
1SDA073674R1
220/240V
1000A, 1200A
1SDA038290R1
110/120V
1400A, 1600A, 2000A
1SDA038292R1
220/240V
1400A, 1600A, 2000A
Catalogue Number
Application
Main-Breaker
Main-Switch
1SDA105099R1
400A, 600A
400A
1SDA105102R1
800A
600A
1SDA105104R1
1000A, 1200A
800A
1SDA038351R1
1400A-1600A-2000A
n/a
For main-modules with lug landings pads on the line side,
use the following compression lugs: