Table 1:  Locations of Wall-Rails: Main-Module

*Underscores in the catalog indicate characters that are variable which don’t impact the dimensions in the table

Catalog Number

Dimensions (inches)

Height

Width

Depth

V2

X2

Main-Breaker Module

RMM_B_4R

47 15/16

20  5/16

11 1/4

12 7/8

35  1/16

RMM_B_6R

47 15/16

20  5/16

11 1/4

12 7/8

35  1/16

RMM_B_8R

47 15/16

20  5/16

11 1/4

12 7/8

35  1/16

RMM_B_10R

47 15/16

20  5/16

11 1/4

12 7/8

35  1/16

RMM_B_12R

47 15/16

20  5/16

11 1/4

12 7/8

35  1/16

RMM_BE_4R

60 1/4

20  5/16

11 1/4

9 7/8

50 3/8

RMM_BE_6R

60 1/4

25  1/16

11 1/4

9  1/16

51  3/16

RMM_BE_8R

60 1/4

25  1/16

11 1/4

9  1/16

51  3/16

RMM_BE_10R

60  7/16

33 5/8

12      

8  1/16

52  7/16

RMM_BE_12R

60  7/16

33 5/8

12      

8  1/16

52  7/16

RMM_BB14R

57  2/16

25 1/8

14 7/8

8  7/16

48 5/8

RMM1BB14RL

60 5/8

38  5/16

24  3/16

8      

52 5/8

RMM1BT14R

59 1/8

25 1/8

14 7/8

30 13/16

28  5/16

RMM_BB14RCLL

60 5/8

38  5/16

24  3/16

8      

52 5/8

RMM_BB16R

57 1/8

25 1/8

14 7/8

8  7/16

48 5/8

RMM_BB16RL

60 5/8

38  5/16

24  3/16

8      

52 5/8

RMM_BT16R

59 1/8

25 1/8

14 7/8

30 13/16

28  5/16

RMM_BB16RCLL

60 5/8

38  5/16

24  3/16

8      

52 5/8

RMM_BB20R

60 5/8

38  5/16

24  3/16

8      

52 5/8

Main-Lug Module

RMM_L4R

48      

13 3/4

6 1/2

15 15/16

32  1/16

RMM_L6R

47 15/16

16 3/4

6 1/2

14  5/16

33 5/8

RMM_L8R

47 15/16

20  5/16

11 1/4

12 7/8

35  1/16

RMM_L12R

47 15/16

20  5/16

11 1/4

12 7/8

35  1/16

RMM_L16R

60 13/16

33 1/8

17 11/16

22 3/8

38 1/2

RMM_L20R

60 13/16

33 1/8

17 11/16

22 3/8

38 1/2

RMM_L12RFTL

60 15/16

28 13/16

11 13/16

22 3/8

38  9/16

RMM_L16RFTL

60 13/16

33 1/8

17 11/16

22 3/8

38 1/2

RMM_L20RFTL

60 13/16

33 1/8

17 11/16

22 3/8

38 1/2

Main Fusible-Switch Module

RMM_F4R

47 15/16

20  5/16

11 1/4

16 7/8

31  1/16

RMM_F6R

54 7/8

20  5/16

12 11/16

19 13/16

35  1/16

RMM_F8R

54 7/8

20  5/16

12 11/16

20 13/16

34  1/16

RMM_FE4RCLL

60 1/4

20  5/16

11 1/4

12 7/8

47 3/8

RMM_FE6RCLL

65  3/16

25  1/16

13      

12 1/2

52 11/16

RMM_FE8RCLL

65  3/16

25  1/16

13      

14 7/8

50  5/16

Pull Boxes

RMM_P4R

43  3/16

16 13/16

7 11/16

11 5/8

31  9/16

RMM_P8R

50  7/16

24 7/8

11  5/16

15  7/16

35      

RMM_P12R

54  9/16

33      

11  5/16

19  9/16

35      

Surge Protection Device

RMM_1SURGE

25 1/8

15 1/4

12 11/16

5  7/16

19 11/16

RMM_2SURGE

25 1/8

15 1/4

10      

5  7/16

19 11/16

RMM_3SURGE

25 1/8

15 1/4

10      

5  7/16

19 11/16

Elbows/ Spacer

RELBOW316N3R

25 1/8

32  3/16

5  5/16

5  7/16

19 11/16

RELBOWE312N3R

25 1/8

24  3/16

5  5/16

5  7/16

19 11/16

RSPACER3124

25 1/8

7 1/4

5  5/16

 - 

 -

Summary of Contents for ReliaMod RMM B 4R

Page 1: ...ones en espa ol v ase la p gina 16 HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH Turn OFF power supplying this equipment before working inside Please read these instructions completely before in...

Page 2: ...Mounting of units Meter module Electrical code or project spec Electrical code or project spec Grade level Utility spec Min meter position Utility spec Max meter position Main module V2 V1 X2 X1 A Y Z...

Page 3: ...52 5 8 RMM_BB20R 60 5 8 38 5 16 24 3 16 8 52 5 8 Main Lug Module RMM_L4R 48 13 3 4 6 1 2 15 15 16 32 1 16 RMM_L6R 47 15 16 16 3 4 6 1 2 14 5 16 33 5 8 RMM_L8R 47 15 16 20 5 16 11 1 4 12 7 8 35 1 16 RM...

Page 4: ...7 8 18 3 8 9 5 8 35 5 16 48 9 16 27 7 16 20 9 16 Commercial Lever Bypass LVBP 225A and 400 Socket RMS_12122CHLBR 54 1 16 19 5 8 9 11 16 24 1 2 29 9 16 n a 4 11 16 RMS_12222CHLBR 54 1 16 19 5 8 9 11 16...

Page 5: ...ttom end walls on main modules can be removed from the enclosure to ease the punching of holes for bot tom fed conduit and conductors the mounting screws to maintain NEMA 3R enclosure rating The embos...

Page 6: ...need to bond the neutral use the bonding jumper supplied with the unit Unfasten from the factory installed position Rotate jumper and fasten to the neutral bus at torque indicated on label in unit Se...

Page 7: ...Trip Unit Default PIN is 00001 The following is a step by step guide for implementing RELT settings and ensuring proper operation of the RELT function for XT7 touch trip units Enter the submenu for th...

Page 8: ...ct Protection Press Enter Scroll down to ON Press Enter arrow pushbutton Scroll down to Threshold MM Press Enter arrow pushbutton Adjust the threshold using UP and Down Arrows pushbuttons Press Enter...

Page 9: ...f Complete the fastening of the breaker to its mounting plate by torquing the mounting screws to 10 in lbf THQL THHQL are plug in type breakers All other breakers are bolt on Installation of A1 breake...

Page 10: ...ker Installation of XT3 Breakers Mount breaker on its plate with the straps aligned with busbars on the meter module Use the mounting screws included in the breaker package to fasten the breaker to th...

Page 11: ...s 1 Gang 2 Gang 3 Gang 4 Gang 5 Gang 6 Gang 1 meter at the top A C A C A C A C A C A C 2 A B A B A B A B A B 3 B C B C B C B C 4 A C A C A C A C 5 A B A B 6 B C Position A C Position A B Position B C...

Page 12: ...ion B C to position A B 4 Install strap in position C 5 Tighten all connections to 170 in lbf Conversion from A C to A B 2 Remove meter barrier at location to convert 3 Remove C phase strap 4 Install...

Page 13: ...and insulation sheet 6 Tighten all connections to 170 in lbf 7 Re install meter barrier Conversion from B C to A B 2 Remove meter barrier at location to convert 3 Remove C phase strap 4 Switch phase...

Page 14: ...meter jaws and disactivate the bypass 6 Replace the ringless meter cover NOTE Meter cover cannot be installed with the lever in the bypass mode Warning Hazardous Voltage can cause serious injury or d...

Page 15: ...h the meter module Remove inch knockout and install sealing screw provided Install utility seal through the hole in the sealing screw and the slot in the hasp Provision for utility seal Provision for...

Page 16: ...de este equipo antes de realizar cualquier trabajo dentro o fuera de l Lea atentamente estas instrucciones antes de instalar o retirar el dispositivo Una instalaci n incorrecta podr a resultar peligro...

Page 17: ...o o especificaci n del proyecto C digo el ctrico o especificaci n del proyecto Nivel de grado Requisito de la empresa de servicio publico Posici n min del medidor Requisito de la empresa de servicio p...

Page 18: ...5 8 38 5 16 24 3 16 8 52 5 8 Modulo principal con zapatas RMM_L4R 48 13 3 4 6 1 2 15 15 16 32 1 16 RMM_L6R 47 15 16 16 3 4 6 1 2 14 5 16 33 5 8 RMM_L8R 47 15 16 20 5 16 11 1 4 12 7 8 35 1 16 RMM_L12R...

Page 19: ...comercial LVBP de 225A y toma de 400A RMS_12122CHLBR 54 1 16 19 5 8 9 11 16 24 1 2 29 9 16 n a 4 11 16 RMS_12222CHLBR 54 1 16 19 5 8 9 11 16 24 1 2 29 9 16 9 5 16 4 11 16 RMS_12322CHLBR 68 1 16 19 5 8...

Page 20: ...venden por separado Conductores de L nea alimentados por el fondo Las paredes inferiores de los m dulos principales pueden retirarse de la caja para facilitar la perforaci n de orificios para conducto...

Page 21: ...nidad Desabrochar desde la posici n de instalaci n en f brica Gire el puente y f jelo al bus neutro al par indicado en la etiqueta de la unidad Fije el puente a la caja con la torniller a suministrada...

Page 22: ...PIN predeterminado es 00001 La siguiente es una gu a paso a paso para implementar los ajustes RELT y garantizar el correcto funcionamiento de la funci n RELT para las unidades de disparo por contacto...

Page 23: ...eleccione Protecci n Pulse Intro Despl cese hasta ON Pulse el bot n de flecha Intro Despl cese hasta Umbral MM Pulse el bot n de flecha Intro Ajuste el umbral con los pulsadores de flecha ARRIBA y ABA...

Page 24: ...la fijaci n del interruptor a su placa de montaje apretando los tornillos de montaje a 10 in lbf THQL THHQL son interruptores autom ticos enchufables Todos los dem s disyuntores son atornillables Ins...

Page 25: ...vez instalados los conductores Formula A2 marco disyuntores XT4 marco disyuntores XT3 marco disyuntores Instalaci n de disyuntores XT3 Monte el disyuntor en su placa con las correas alineadas con las...

Page 26: ...iento Phase Link 3 8 Herrajes 1 Desconecte la alimentaci n del equipo Conversi n de A C a B C 2 Retire la correa en la posici n A 3 Instale el enlace de fase el aislamiento y el perno 3 8 en la posici...

Page 27: ...as las conexiones a 170 in lbf Conversi n de A C a A B 2 Quitar la barrera del contador en el lugar a convertir 3 Quitar la correa de la fase C 4 Instale el enlace de fase el aislamiento y el perno 3...

Page 28: ...te todas las conexiones a 170 in lbf 7 Volver a instalar la barrera de contadores Conversi n de B C a A B 2 Quitar la barrera del contador en el lugar a convertir 3 Quitar la correa de la fase C 4 Int...

Page 29: ...mand bula a la derecha Funci n de derivaci n de la palanca Instalaci n o sustituci n delcontador en un m dulo contador de derivaci n de palanca PRECAUCI N Debe ser realizado por personal de servicio a...

Page 30: ...lado suministrado con el m dulo contador Retire el orificio ciego de de pulgada e instale el tornillo de sellado suministrado Instale la junta de estanqueidad a trav s del orificio del tornillo de est...

Reviews: