Transformer module (TRM)
Chapter 13
Hardware modules
3
Transformer module (TRM)
3.1
Design
A transformer input module can have up to 10 input transformers. The actual number depends
on the type of terminal. Terminals including only current measuring functions only have current
inputs. Fully equipped the transformer module consists of:
•
Five voltage transformers
•
Five current transformers
The inputs are mainly used for:
•
Phase currents
•
Residual current of the protected line
•
Residual current of the parallel circuit (if any) for compensation of the effect of
the zero sequence mutual impedance on the fault locator measurement or residual
current of the protected line but from a parallel core used for CT circuit supervi-
sion function or independent earth fault function.
•
Phase voltages
•
Open delta voltage for the protected line (for an optional directional earth-fault
protection)
•
Phase voltage for an optional synchronism and energizing check.
3.2
Technical data
Table 211: TRM - Energizing quantities, rated values and limits
Quantity
Rated value
Nominal range
Current
I
r
= 1 or 5 A
(0.2-30)
×
I
r
Operative range
(0.004-100) x I
r
Permissive overload
4
×
I
r
cont.
100
×
I
r
for 1 s
*)
Burden
< 0.25 VA at I
r
= 1 or 5 A
Ac voltage for the terminal
U
r
= 110 V **)
U
r
= 220 V **)
100/110/115/120 V
200/220/230/240 V
Operative range
(0.001-1.5) x U
r
Permissive overload
2.3
×
U
r
phase-earth, cont.
3.0 x U
r
phase-earth, for 1 s
Burden
< 0.2 VA at U
r
Frequency
f
r
= 50/60 Hz
+/-10%
*)
max. 350 A for 1 s when COMBITEST test switch is included.
**) The rated voltage of each individual voltage input U1 to U5 is U
r
/√
3
Summary of Contents for REL 501-C1 2.5
Page 1: ...Technical reference manual Line distance protection terminal REL 501 C1 2 5 ...
Page 2: ......
Page 26: ...14 Introduction to the technical reference manual Chapter 1 Introduction ...
Page 42: ...30 Technical data Chapter 2 General ...
Page 66: ...54 Blocking of signals during test BST Chapter 3 Common functions ...
Page 142: ...130 Time delayed overvoltage protection TOV Chapter 6 Voltage ...
Page 162: ...150 Autorecloser AR Chapter 9 Control ...
Page 174: ...162 Event function EV Chapter 10 Logic ...
Page 210: ...198 Serial communication Chapter 12 Data communication ...
Page 226: ...214 Serial communication modules SCM Chapter 13 Hardware modules ...
Page 230: ...218 Terminal diagrams Chapter 14 Diagrams Figure 87 REL 501 C1 with DC switch ...
Page 234: ...222 Terminal diagrams Chapter 14 Diagrams ...
Page 237: ......