174
Supervision of AC input quantities (DA)
Chapter 11
Monitoring
EnAlarms
Off, On
Off
-
Set to 'On' to activate alarm supervision for
I1 - I5 (produces an immediate event at oper-
ation of any alarm monitoring element, when
On)
HiAlarm
0-99999
Step: 1
900
A
High Alarm level for I1 - I5
HiWarn
0-99999
Step: 1
800
A
High Warning level for I1 - I5
LowWarn
0-99999
Step: 1
200
A
Low Warning level for I1 - I5
LowAlarm
0-99999
Step: 1
100
A
Low Alarm level for I1 - I5
RepInt
0-3600
Step: 1
0
s
Time between reports for I1 - I5 in seconds.
Zero = Off (duration of time interval between
two reports at periodic reporting function.
Setting to 0 disables the periodic reporting)
EnDeadB
Off, On
Off
-
Enable amplitude dead band supervision for
I1 - I5
DeadBand
0-99999
Step: 1
50
A
Amplitude dead band for I1 - I5
EnIDeadB
Off, On
Off
-
Enable integrating dead band supervision for
I1 - I5
IDeadB
0-99999
Step: 1
10000
A
Integrating dead band for I1 - I5
EnDeadBP
Off, On
Off
-
Enable periodic dead band reporting I1 - I5
Mean phase-to-phase voltage measuring
channel U: DA11-
Operation
Off, On
Off
-
Operating mode for DAnn function
Hysteres
0.0-1999.9
Step: 0.1
5.0
kV
Alarm hysteresis for U
EnAlRem
Off, On
On
-
Immediate event when an alarm is disabled
for U (produces an immediate event at reset
of any alarm monitoring element, when On)
EnAlarms
Off, On
On
-
Set to 'On' to activate alarm supervision for U
(produces an immediate event at operation
of any alarm monitoring element, when On)
HiAlarm
0.0-1999.9
Step: 0.1
220.0
kV
High Alarm level for U
HiWarn
0.0-1999.9
Step: 0.1
210.0
kV
High Warning level for U
LowWarn
0.0-1999.9
Step: 0.1
170.0
kV
Low Warning level for U
LowAlarm
0.0-1999.9
Step: 0.1
160.0
kV
Low Alarm level for U
Parameter
Range
Default
Unit
Description
Summary of Contents for REL 501-C1 2.5
Page 1: ...Technical reference manual Line distance protection terminal REL 501 C1 2 5 ...
Page 2: ......
Page 26: ...14 Introduction to the technical reference manual Chapter 1 Introduction ...
Page 42: ...30 Technical data Chapter 2 General ...
Page 66: ...54 Blocking of signals during test BST Chapter 3 Common functions ...
Page 142: ...130 Time delayed overvoltage protection TOV Chapter 6 Voltage ...
Page 162: ...150 Autorecloser AR Chapter 9 Control ...
Page 174: ...162 Event function EV Chapter 10 Logic ...
Page 210: ...198 Serial communication Chapter 12 Data communication ...
Page 226: ...214 Serial communication modules SCM Chapter 13 Hardware modules ...
Page 230: ...218 Terminal diagrams Chapter 14 Diagrams Figure 87 REL 501 C1 with DC switch ...
Page 234: ...222 Terminal diagrams Chapter 14 Diagrams ...
Page 237: ......