175
Supervision of AC input quantities (DA)
Chapter 11
Monitoring
RepInt
0-3600
Step: 1
0
s
Time between reports for U in seconds. Zero
= Off (duration of time interval between two
reports at periodic reporting function. Setting
to 0 disables the periodic reporting
EnDeadB
Off, On
Off
-
Enable amplitude dead band supervision for
U
DeadBand
0.0-1999.9
Step: 0.1
5.0
kV
Amplitude dead band for U
EnIDeadB
Off, On
Off
-
Enable integrating dead band supervision for
U
IDeadB
0.0-1999.9
Step: 0.1
10.0
kV
Integrating dead band for U
EnDeadBP
Off, On
Off
-
Enable periodic dead band reporting U
Mean current measuring channel I
:
DA12-
Operation
Off, On
Off
-
Operating mode for DAnn function
Hysteres
0-99999
Step: 1
50
A
Alarm hysteresis for I
EnAlRem
Off, On
On
-
Immediate event when an alarm is disabled
for I (produces an immediate event at reset
of any alarm monitoring element, when On)
EnAlarms
Off, On
Off
-
Set to 'On' to activate alarm supervision for I
(produces an immediate event at operation
of any alarm monitoring element, when On)
HiAlarm
0-99999
Step: 1
900
A
High Alarm level for I
HiWarn
0-99999
Step: 1
800
A
High Warning level for I
LowWarn
0-99999
Step: 1
200
A
Low Warning level for I
LowAlarm
0-99999
Step: 1
100
A
Low Alarm level for I
RepInt
0-3600
Step: 1
0
s
Time between reports for I in seconds. Zero
= Off (duration of time interval between two
reports at periodic reporting function. Setting
to 0 disables the periodic reporting)
EnDeadB
Off, On
Off
-
Enable amplitude dead band supervision for
I
DeadBand
0-99999
Step: 1
50
A
Amplitude dead band for I
EnIDeadB
Off, On
Off
-
Enable integrating dead band supervision for
I
IDeadB
0-99999
Step: 1
10000
A
Integrating dead band for I
EnDeadBP
Off, On
Off
-
Enable periodic dead band reporting I
Parameter
Range
Default
Unit
Description
Summary of Contents for REL 501-C1 2.5
Page 1: ...Technical reference manual Line distance protection terminal REL 501 C1 2 5 ...
Page 2: ......
Page 26: ...14 Introduction to the technical reference manual Chapter 1 Introduction ...
Page 42: ...30 Technical data Chapter 2 General ...
Page 66: ...54 Blocking of signals during test BST Chapter 3 Common functions ...
Page 142: ...130 Time delayed overvoltage protection TOV Chapter 6 Voltage ...
Page 162: ...150 Autorecloser AR Chapter 9 Control ...
Page 174: ...162 Event function EV Chapter 10 Logic ...
Page 210: ...198 Serial communication Chapter 12 Data communication ...
Page 226: ...214 Serial communication modules SCM Chapter 13 Hardware modules ...
Page 230: ...218 Terminal diagrams Chapter 14 Diagrams Figure 87 REL 501 C1 with DC switch ...
Page 234: ...222 Terminal diagrams Chapter 14 Diagrams ...
Page 237: ......