149
Autorecloser (AR)
Chapter 9
Control
Table 152: AR - Autorecloser
Maximum trip pulse duration, tTrip (longer trip
pulse durations will either extend the dead
time or interrupt the reclosing sequence)
0.000-60.000 s in steps of 1 ms
±
0.5%
±
10 ms
Maximum wait time for release from Master,
tWaitForMaster
0.0-90000.0 s in steps of 0.1 s
±
0.5%
±
10 ms
Maximum wait time between shots, tAutoWait 0.000-60.000 s in steps of 1 ms
±
0.5%
±
10 ms
Time delay before indicating reclosing unsuc-
cessful, tUnsuc
0.0-90000.0 s in steps of 0.1 s
±
0.5%
±
10 ms
Time CB must be closed before AR becomes
ready for a reclosing cycle, tCBClosed
0.000-60.000 s in steps of 1 ms
±
0.5%
±
10 ms
Parameter
Value
Reclosing shots
1-4
Programs
Three pole trip: 1
Single, two and three pole trip: 6
Number of autoreclosers
Up to six depending on terminal type (dif-
ferent terminal types support different CB
arrangements and numbers of bays)
Breaker closed before start
5 s
Parameter
Setting range
Accuracy
Summary of Contents for REL 501-C1 2.5
Page 1: ...Technical reference manual Line distance protection terminal REL 501 C1 2 5 ...
Page 2: ......
Page 26: ...14 Introduction to the technical reference manual Chapter 1 Introduction ...
Page 42: ...30 Technical data Chapter 2 General ...
Page 66: ...54 Blocking of signals during test BST Chapter 3 Common functions ...
Page 142: ...130 Time delayed overvoltage protection TOV Chapter 6 Voltage ...
Page 162: ...150 Autorecloser AR Chapter 9 Control ...
Page 174: ...162 Event function EV Chapter 10 Logic ...
Page 210: ...198 Serial communication Chapter 12 Data communication ...
Page 226: ...214 Serial communication modules SCM Chapter 13 Hardware modules ...
Page 230: ...218 Terminal diagrams Chapter 14 Diagrams Figure 87 REL 501 C1 with DC switch ...
Page 234: ...222 Terminal diagrams Chapter 14 Diagrams ...
Page 237: ......