Communication
38
The format of the input assembly is:
The value of Input I/O 1 to 9 is read from the data word or drive
parameter defined by Input I/O Par 1 to 9 respectively. See
chapter
Programming.
Input I/O 10 to 32 can be configured through the Vendor Specific
ControlNet Configuration object, Class 0x91.
Note:
the max number of output I/O’s supported by the drive
depends on the drive type and application.
Note:
If the BASIC SPEED CONTROL or the EXTENDED SPEED
CONTROL assembly is used, it must be ensured that the fieldbus
is selected as the drive control source and fieldbus specific
(Generic Drive profile) Control/Status Word format is selected
instead of ABB Drives profile.
Instance 103 (Input assembly)
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Input I/O 1 (Low Byte)
1
Input I/O 1 (High Byte)
2
Input I/O 2 (Low Byte)
3
Input I/O 2 (High Byte)
4
Input I/O 3 (Low Byte)
5
Input I/O 3 (High Byte)
6
Input I/O 4 (Low Byte)
7
Input I/O 4 (High Byte)
8
Input I/O 5 (Low Byte)
9
Input I/O 5 (High Byte)
10
Input I/O 6 (Low Byte)
11
Input I/O 6 (High Byte)
12
Input I/O 7 (Low Byte)
13
Input I/O 7 (High Byte)
14
Input I/O 8 (Low Byte)
15
Input I/O 8 (High Byte)
16
Input I/O 9 (Low Byte)
17
Input I/O 9 (High Byte)
Summary of Contents for RCNA-01
Page 1: ...ABB Drives User s Manual ControlNet Adapter Module RCNA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 9: ...Table of contents 9 Technical data 65 RCNA 01 65 Fieldbus link 66 ...
Page 10: ...Table of contents 10 ...
Page 14: ...Introduction 14 ...
Page 20: ...Mechanical installation 20 ...
Page 32: ...Programming 32 ...
Page 60: ...Communication 60 ...
Page 67: ......