Note
NC means those pins are reserved. They cannot be electrically connected to any
external signal, ground, or voltage.
Description
Pin
High side terminal of Emergency stop output Channel 1.
Low side terminal of Emergency stop output Channel 1.
ESOUT1-
High side terminal of Emergency stop output Channel 2.
Low side terminal of Emergency stop output Output Channel 2.
ESOUT2-
24 V power supplied by robot controller for motors on lamp and
motors on push button use only. It must not be used for any other
functions.
24V_MON
Motors on lamp output interface. The max sink current is 50mA.
MON_LAMP
Motors on push button input interface.
MON_PB
Note
The device connected to the ESOUT pins shall fulfill the IEC 61131-2 type 1 Input.
Note
Logic low of Emergency stop output shall be recognized as Emergency stop
triggered.
Note
The maximum length of the cable connected to the ESOUT pins shall be 10 m.
Note
The cable shall be protected from external EM disturbance, suggested to use
separate multicore cables.
Note
The FlexPendant connector can only be used to connect a FlexPendant and
CANNOT be used to connect any other devices.
All external safety devices must be connected from the customer interface on
robot signal exchange proxy.
Continues on next page
96
Product manual - OmniCore C90XT
3HAC073706-001 Revision: D
© Copyright 2020-2021 ABB. All rights reserved.
3 Installation and commissioning
3.5.9 Descriptions for connectors
Continued
Summary of Contents for OmniCore C90XT
Page 1: ...ROBOTICS Product manual OmniCore C90XT ...
Page 50: ...This page is intentionally left blank ...
Page 350: ...This page is intentionally left blank ...
Page 354: ...This page is intentionally left blank ...
Page 412: ...This page is intentionally left blank ...
Page 444: ...This page is intentionally left blank ...
Page 448: ......
Page 449: ......