4.5.5 Function test of auto stop
Performing the function test
Note
Action
Start the robot system and change the op-
erating mode to auto mode.
1
The test is passed if the event message
20205 Auto stop open
appears in the event
log.
Activate the auto stop, for example by
opening the connected robot cell door,
which has interlock connection with auto
stop.
2
If the event message
20205 Auto stop
open
does not appear or if the event mes-
sage
20225 Auto stop conflict
appears in
the event log, then the test has failed and
the root cause of the failure must be found.
Product manual - OmniCore C90XT
169
3HAC073706-001 Revision: D
© Copyright 2020-2021 ABB. All rights reserved.
4 Maintenance
4.5.5 Function test of auto stop