66
MOU NTI NG A N D OPE R ATI ON M A N UA L
I N D O O R A I R S W I TC H - D I S CO N N EC TO R , N A L /N A L F/ V R
Rated
system
voltage
[kV]
Transformer
Fuse-link
Switch-fuse
combination
dedicated
type
Rated
power S
R
[kVA]
Relative
impedance
voltage
uk [%]
Rated
current I
R
[A] 100%
Rated
current I
R
[A] 120 %
Type
Rated
voltage
U
R
[kV]
Rated
normal
current
I
R
[A]
Length
e [mm] Catalogue number
10-12
50
4
2.9
3.5
CEF-S
6/12
10
292 1YMB741216M2611
NALF 12 kV
75
4
4.3
5.2
CEF-S
6/12
16
292 1YMB741218M2611
100
4
5.8
6.9
CEF-S
6/12
20
292 1YMB741219M2611
125
4
7.2
8.7
CEF-S
6/12
20
292 1YMB741219M2611
160
4
9.2
11.1
CEF-S
6/12
25
292 1YMB741221M2611
200
4
11.5
13.9
CEF-S
6/12
40
292 1YMB741225M2611
250
4
14.4
17.3
CEF-S
6/12
40
292 1YMB741225M2611
315
4
18.2
21.8
CEF-S
6/12
50
292 1YMB741227M2611
400
4
23.1
27.7
CEF-S
6/12
63
292 1YMB741229M2611
500
4
28.9
34.6
CEF-S
6/12
63
292 1YMB741229M2611
630
1)
4
30.3
36.4
CEF-S
6/12
63
292 1YMB741229M2611
20-24
75
4)
4
2.2
2.6
CEF-S
10/24
10
442 1YMB742416M4611
NALF 24 kV
100
4
2.9
3.5
CEF-S
10/24
10
442 1YMB742416M4611
125
4
3.6
4.3
CEF-S
10/24
16
442 1YMB742418M4611
160
4
4.6
5.5
CEF-S
10/24
16
442 1YMB742418M4611
200
4
5.8
6.9
CEF-S
10/24
20
442 1YMB742419M4611
250
4
7.2
8.7
CEF-S
10/24
20
442 1YMB742419M4611
315
4
9.1
10.9
CEF-S
10/24
25
442 1YMB742421M4611
400
4
11.5
13.9
CEF-S
10/24
40
442 1YMB742425M4611
500
4
14.4
17.3
CEF-S
10/24
40
442 1YMB742425M4611
630
4
18.2
21.8
CEF-S
10/24
50
442 1YMB742425M4611
800
5
23.1
27.7
CEF-S
10/24
50
442 1YMB742425M4611
1000
2)
5
24.1
28.9
CEF-S
10/24
50
442 1YMB742425M4611
30-36
75
4)
4
1.4
1.7
CEF-S
30/40.5
6.3
537 1YMB744014M5611
NALF Wind
36 kV
100
4)
4
1.9
2.3
CEF-S
30/40.5
6.3
537 1YMB744014M5611
125
4
2.4
2.9
CEF-S
30/40.5
6.3
537 1YMB744014M5611
160
4
3.1
3.7
CEF-S
30/40.5
10
537 1YMB744016M5611
200
4
3.8
4.6
CEF-S
30/40.5
16
537 1YMB744018M5611
250
4
4.8
5.8
CEF-S
30/40.5
16
537 1YMB744018M5611
315
4
6.1
7.3
CEF-S
30/40.5
20
537 1YMB744019M5611
400
4
7.7
9.2
CEF-S
30/40.5
40
537 1YMB744025M5811
500
4
9.6
11.5
CEF-S
30/40.5
40
537 1YMB744025M5811
630
4
12.1
14.5
CEF-S
30/40.5
40
537 1YMB744025M5811
800
5
15.4
18.5
CEF-S
30/40.5
40
537 1YMB744025M5811
1000
5
19.2
23.1
CEF-S
30/40.5
40
537 1YMB744025M5811
1250
5
24.1
28.9
CEF-S
30/40.5
40
537 1YMB744025M5811
1600
6
30.8
37.0
CEF-S
30/40.5
50
537 1YMB744027M5811
2000
6
38.5
46.2
CEF-S
30/40.5
63
537 1YMB744029M5811
2500
6
48.1
57.7
CEF-S
30/40.5
63
537 1YMB744029M5811
3000
3)
6
48.1
57.7
CEF-S
30/40.5
63
537 1YMB744029M5811
Reference list for ABB CEF-S fuse-link selection for transformer protection with 100% and 120 % load
—
1)
- rated voltage 12 kV,
2)
- rated voltage 24 kV,
3)
- rated voltage 36 kV,
4)
fuse link is not able to clear independently transformer secondary side terminals short circuit current