Start-up 43
09
RPDO1-EV time
Defines the event time (time-out time) for the
Rx PDO1 in the asynchronous transmission
mode. If the Rx PDO1 communication between
the adapter module and the bus master fails,
the adapter module sets the communication
between the module and the drive to the off-line
mode.
Event timer (time-out timer) elapses as a
multiple of 1 ms of the entry of this parameter.
Note:
The time-out supervision is activated
upon a successful reception of an Rx PDO1.
0
=
Disable
0
= Disable
Time-out supervision is disabled.
1…65535 (ms)
Event time in ms
10
TPDO1-COB-ID
Defines the COB-ID for Tx PDO1.
Note:
It is recommended to use the default
COB-ID.
1
=
Default
0
= Disable
Tx PDO1 is not valid (disabled). COB-ID is
800 Node-ID.
1
= Default
Tx PDO1 is valid and configured to use the
default COB-ID (180h + Node-ID).
385…1407
(dec) =
181h … 57Fh
Tx PDO1 is valid and configured to use a
custom COB-ID defined with this parameter.
COB-ID must be within the allowed PDO COB-
ID range (181h - 57Fh).
No. Name/Value
Description
Default
setting
Summary of Contents for FCAN-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FCAN 01 CANopen adapter module User s manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 14: ...14 Safety instructions ...
Page 30: ...30 Mechanical installation ...
Page 36: ...36 Electrical installation ...
Page 81: ...Start up 81 ...
Page 82: ...82 Start up 8 Configure the FCAN 01 properties Select the node boot up sequence ...
Page 108: ...108 Communication profiles ...
Page 152: ...152 Communication protocol ...
Page 156: ...156 Diagnostics ...
Page 160: ...160 Technical data ...
Page 164: ...164 Appendix A Dictionary structure and entries ...
Page 173: ...Appendix B CANopen error codes 173 FFFF Manufacturer specific Error code hex Meaning ...