Start-up 41
06
T16 scale
Defines the reference multiplier/actual value
divisor for the adapter module. The parameter
is effective only when the Transparent 16 profile
is selected AND the drive is using the native
communication profile (for example, DCU or
FBA) and a 16-bit transparent Reference
1/Actual value 1.
With an ACS355 drive, the speed reference
from the PLC is multiplied by the value of this
parameter plus one. For example, if the
parameter has a value of 99 and a reference of
1000 given by the master, the reference will be
multiplied by 99 + 1 = 100 and forwarded to the
drive as 100000. According to the DCU profile,
this value is interpreted as a reference of 100
rpm in the drive.
With ACSM1, ACS850 and ACS880, setting
this parameter to 65535 provides the
approximation of 1
≈
1 rpm.
99
0…65535
Reference multiplier/actual value divisor
No. Name/Value
Description
Default
setting
Summary of Contents for FCAN-01
Page 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FCAN 01 CANopen adapter module User s manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 14: ...14 Safety instructions ...
Page 30: ...30 Mechanical installation ...
Page 36: ...36 Electrical installation ...
Page 81: ...Start up 81 ...
Page 82: ...82 Start up 8 Configure the FCAN 01 properties Select the node boot up sequence ...
Page 108: ...108 Communication profiles ...
Page 152: ...152 Communication protocol ...
Page 156: ...156 Diagnostics ...
Page 160: ...160 Technical data ...
Page 164: ...164 Appendix A Dictionary structure and entries ...
Page 173: ...Appendix B CANopen error codes 173 FFFF Manufacturer specific Error code hex Meaning ...