42 Start-up
07
RPDO1-COB-ID
Defines the COB-ID for Rx PDO1.
Note:
It is recommended to use the default
COB-ID.
1
0
= Disable
Rx PDO1 is not valid (disabled). COB-ID is
800 Node-ID.
1
= Default
Rx PDO1 is valid and configured to use the
default COB-ID (200h + Node-ID).
385…1407
(dec) =
181h … 57Fh
Rx PDO1 is valid and configured to use a
custom COB-ID defined with this parameter.
COB-ID must be within the allowed PDO COB-
ID range (181h - 57Fh).
08
RPDO1-TR type
Defines the Rx PDO1 transmission type. See
chapter
Appendix A – Dictionary structure and
.
255
0…255 (dec)
Rx PDO1 transmission type. See section
Description of transmission type
on page
No. Name/Value
Description
Default
setting