BACNET BINARY VALUES
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
DEFAULT VALUES
IMP STG. MET STG.
45
Yes
balanceModeLo
If set to TRUE, Flow will be recorded to
LO_KFactor
If set to FALSE, KFactor will be recorded to
LO_KFactor
On
Off
0
0
88
No
fanStatus
If UI4 is set up for a fan status, displays
current fan status.
On
Off
0
0
95
Yes
sliderEnable
Enable the sliderSpanStpt (A138) to be used
for UI2.
Enable
Disable
0
0
97
No
occOvr
When the occupied override is active.
On
Off
0
0
113
No
coolMode
Will be On if the unit is in cooling mode.
On
Off
114
No
heatMode
Will be On if the unit is in heating mode.
On
Off
117
Yes
remoteZoneTempEnb
Enable the remoteZoneTemp as the active
zone temperature.
On
Off
0
0
118
No
ventMode
120
No
occMode
Will be On if the unit is in occupied mode.
On
Off
124
No
UI1_ZoneTempFailure
If UI1 is being used as the active zone
temperature and the temperature reading is
out of range, the alarm will be enabled.
On
Off
0
0
127
No
fanAlarm
If UI4 is used as the fan status, and the fan is
commanded on and the fan status is open, the
alarm will be enabled.
On
Off
0
0
161
No
occSensorCmd
If an input is set up for an occupancy sensor,
the active status of the occupancy sensor.
On
Off
0
0
164
Yes
CBTStatStptEnb
CBT-Stat lockout that prevents user
adjustment of setpoints. On = locked out.
On
Off
0
0
168
Yes
intScheduleEnb
Enable the internal BACnet schedule. Disables
occCmd (A269).
On
Off
0
0
194
No
highCO2Alarm
If the CO2Demand is above 50% for more than
10 minutes, enable the alarm.
On
Off
0
0
196
No
lowZoneTempAlarm
If the active Zone Temperature is below the
active heating setpoint for more than 15
minutes, enable the alarm.
On
Off
0
0
198
Yes
reverseDO09
Reverse the operation of digital output DO09
On
Off
0
0
200
Yes
reverseDO10
Reverse the operation of digital output DO10
On
Off
0
0
202
Yes
reverseDO11
Reverse the operation of digital output DO11
On
Off
0
0
204
Yes
balanceModeHi
If set to TRUE, Flow will be recorded to
HI_KFactor
If set to FALSE, KFactor will be recorded to
HI_KFactor
On
Off
0
0
205
Yes
reverseAO14
Reverse the operation of analog output AO14
On
Off
0
0
206
Yes
reverseAO15
Reverse the operation of analog output AO15
On
Off
0
0
208
No
UI3_DischargeTempFailure
If UI3 is used as the active discharge air
temperature and the temperature reading is
out of range, the alarm will be enabled.
On
Off
0
0
214
No
lowAirFlowAlarm
If the active airflow is more than 30% below
the active airflow setpoint for more than 5
minutes, enable the alarm.
On
Off
0
0
217
No
lowDischAirTempAlarm
If the discharge air temperature is more than
15 degrees below the discharge air
temperature setpoint for more than 10
minutes, enable the alarm.
On
Off
0
0
219
No
airflowCalibrationAlarm
If the active airflow is more than 10% higher
than the maximum cooling flow setpoint for
than 10 minutes, enable the alarm.
On
Off
0
0
221
No
leakingDamperAlarm
If the damper command is at 0% and the
active airflow is above the minHeatFlowStpt
(A230) for more than 10 min, enable the alarm.
On
Off
0
0