FBVi-2U4-4T |
Control Sequence
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
91
M
AN
01
48
re
v 5
UNIT STATUS AND GRAPHIC POINTS
UNIT STATUS
For information on the current unit function, these points can be enumerated to display on graphic
screens.
Occupancy status is displayed from
occStatus (A316)
•
0=Unocc
•
1=Occ
•
3=Standby
•
4=SetbackMode
•
8=SetupMode
Unit status is displayed from
unitStatus (A317)
•
1=CoolMode
•
2=VentMode
•
4=HeatMode
HVAC Mode status is displayed from
HVACModeStatus (A295)
•
0 = Auto
•
1 = Morning Warm Up
•
2 = Morning Cool Down
•
4 = Heat Only
•
8 = Cool Only
•
16 = Shed
•
32 = Fire
•
64 = Purge
GRAPHIC POINTS
Extra points are available for use in graphic generation. These are optional and do not influence the
operation of the unit. Used in Integra applications.
graphic_variableFanSignal (A315)
Use with analog graphics. If
fanConfig (A54)
is set up as a variable series fan or a variable parallel fan, and
the signal from AO15 is greater than 0, the graphic will be enabled.
graphic_variableFanEnable (D266)
Use with a digital graphic. If
fanConfig (A54)
is set up as a variable series fan or a variable parallel fan,
and the signal from AO15 is greater than 0, the graphic will be enabled.
graphic_digitalFan (D261)
Use with a digital graphic. If
fanConfig (A54)
is set up as an on/off series or on/off parallel fan, and
digital output DO12 is On, the graphic will be enabled.
graphic_showPerimeterHeat (D265)
Use with a digital graphic. If
stagesOfPerimeterHeat (A75)
is greater than 0, enable the graphic.
graphic_Stg3HeatDigital (D264)
Use with digital graphics. If
heatConfig (A4)
is set for 3 stages of heat, and digital output DO11 is On, the
graphic will be enabled.
graphic_Stg2HeatDigital (D268)