FBVi-2U4-4T |
Control Sequence
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
92
M
AN
01
48
re
v 5
Use with digital graphics. If
heatConfig (A4)
is set for 2 stages of heat, and digital output DO10 is On, the
graphic will be enabled.
graphic_Stg1HeatDigital (D267)
Use with digital graphics. If
heatConfig (A4)
is set for 1, 2, or 3 stages of heat, and digital output DO09 is
On, the graphic will be enabled.
graphic_Stg2HeatSignal (A318)
Use with analog graphics. If
heatConfig (A4)
is set for 2 stages of heat, and digital output DO10 is On,
and
stg2OutType (A2)
is a voltage signal, and
fanConfig (A54)
is not set for a variable fan, the graphic will
be enabled.
graphic_Stg1HeatSignal (A327)
Use with analog graphics. If
heatConfig (A4)
is set for 3 stages of heat, and digital output DO10 is On,
and
stg2OutType (A2)
is a voltage signal, the graphic will be enabled.