FBVi-2U4-4T |
Control Sequence
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
87
M
AN
01
48
re
v 5
TEST AND BALANCE
You can balance the box using
Aero
ᴮᵀ
(see
MAN0144 Aero
ᴮᵀ
VAV Phone App
)
, or
CXpro
ᴴᴰ
(see
MAN0133
CXpro
ᴴᴰ
)
.
A point has been setup to allow test and balance commands to be sent to individual boxes, or groups of
boxes, to set the primary air damper to max Flowrate,
deadband
Flowrate, fully open, fully closed, etc.
These commands may be used to calibrate the airflow sensor and balance the boxes. Before balancing
the box, the unit should be in occupied mode, and the
HVACmodeCmd (A287)
should be in Auto.
SETTING INITIAL BOX SIZE
Before balancing is available, an initial box size can be set to generate a starting K-factor. After balancing,
this initial K-factor will be replaced with the balanced K-factor.
Set box size with the
boxSize (A144)
analog setpoint:
•
1 = 4" Box
•
2 = 5" Box
•
3 = 6" Box
•
4 = 8" Box
•
5 = 10" Box
•
6 = 12" Box
•
7 = 14" Box
•
8 = 16" Box
ZEROING AIRFLOW SENSOR
The
FBVI-2U4-4T
comes from the factory with the airflow sensor zeroed. To compensate for possible air
leakage around the damper, users can zero the airflow sensor in the field. To zero the airflow sensor,
users will need to do the following:
1.
Drive damper to the closed position by setting
flowOverride (A258)
to 6 (fullClosed).
2.
After the damper has fully shut,
set
zeroAirflow (D227)
to ON. After 10 sec. it will record the offset.
After 10 seconds
zeroAirflow (D227)
will be automatically set back to off and the airflow sensor will now
be zeroed. Be sure to set
flowOverride (A258)
to 0 (Auto) when finished with this step. The airflow
offset calculation can be read at
airflowOffset (A3).
AIRFLOW CALIBRATION PROCEDURE
K-factor settings can be manually entered:
1.
For Single Point or the High K-factor, set
balanceModeHi (D204)
to
FALSE
and enter the K-factor
in the
KFactorFlowHI (A214)
analog setpoint.
2.
For the Low K-factor, set
balanceModeLo (D45)
to
FALSE
and enter the K-factor in the
KFactorFlowLO (A245)
analog setpoint.
3.
The K-Factor that is used for flow will be displayed at
activeKfactor (A293)
4.
The current flow will be displayed at
activeAirflow (A250)
5.
To reset the K-factor back to the initial box size K-factor, enter 0 when manually entering both
low and high K-factors.