BACNET ANALOG VALUES
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
UNITS AND DEFAULT VALUES
IMPERIAL STG.
METRIC STG.
1
Yes
stg1OutType
Output hardware setup for first stage of Heat
1 = 0-10V
2 = 2-10V
3 = Float
4 = Custom for AO14
0
no-units
0
no-units
2
Yes
stg2OutType
Output hardware setup for second stage of Heat
1 = 0-10V
2 = 2-10V
4 = Custom for AO15
0
no-units
0
no-units
3
No
airflowOffset
After zeroing airflow, calculated offset.
Pa
Pa
4
Yes
heatConfig
Configuration for the heat staging. Calculated with
the CXPro Bacnet commission tool. Add values
together for the total.
0 = no heat
1 = one stage heat
2 = two stages heat
4 = three stages heat
16 = perimeter heat primary
32 = duct hand perimeter simultaneous operation
64 = dual max control on
0
no-units
0
no-units
6
No
terminalLoad
The current terminal load. -100 to +100%
%
%
31
No
dischargeAirTempStpt
Calculated discharge air temperature setpoint.
Minimum is 50°F (10°C)
°F
°C
34
Yes
highDuctTempLockout
If duct temperature is above setpoint, heat will be
locked out until it falls below 120°F (49°C).
180
°F
82
°C
54
Yes
fanConfig
Configuration for fan control.
0 = No Fan
1 = On/Off Series Fan
2 = On/Off Parallel Fan
4 = Variable Series Fan
8 = Variable Parallel Fan
0
no-units
0
no-units
75
Yes
stagesOfPerimeterHeat
If the unit is configured for heat control with
heatConfig
, set the number of stages for perimeter
heat. Perimeter heat will directly control zone
temperature. Set 0-3 stages.
0
no-units
0
no-units
117
No
netOccCmd
Used for network assignment of the occCmd . Used
when utilizing Tx modules. Not for BACnet use.
no-units
no-units
119
No
netHVACMode
Used for network assignment of the HVACMode.
Used when utilizing Tx modules. Not for BACnet use.
no-units
no-units
123
Yes
occCoolStpt
Set the occupied Cooling Setpoint.
74
°F
23
°C
124
Yes
occHeatStpt
Set the occupied Heating Setpoint
72
°F
21
°C
125
Yes
unoccCoolStpt
Set the unoccupied Cooling Setpoint
80
°F
29
°C
126
Yes
unoccHeatStpt
Set the unoccupied Heating Setpoint
65
°F
14
°C
133
Yes
maxSliderRange
When a potentiometer is used on UI2 for setpoint
offset, the maximum Ohm range of the span.
5K
Ohms
5K
Ohms
138
Yes
sliderSpanStpt
The allowable temperature range for the
potentiometer is used on UI2 . 4 = +2 deg and -2 deg
from setpoint.
4
°F
4
°C
144
Yes
boxSize
Box size of the VAV. Sets an initial KFactor before
balancing. Once the box is balanced, this value is
replaced.
1 = 4"Box
2 = 5"Box
3 = 6"Box
4 = 8"Box
5 = 10"Box
6 = 12"Box
7 = 14"Box
8 = 16"Box
4
no-units
4
no-units
146
Yes
standbyOffset
When the unit is in Standby Mode, the occupied
heating and cooling setpoints will be offset by this
amount.
Occupied cool stpt + offset
Occupied heat stpt - offset
3
°F
3
°C