POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
UNITS AND DEFAULT VALUES
IMPERIAL STG.
METRIC STG.
314
No
UI2_InputConfig
Used for input reset. Not for BACnet use
no-units
no-units
315
No
graphic_VariableFanSignal
Used for graphics. Analog variable fan signal.
316
No
occStatus
Shows current occupancy status.
0=Unocc
1=Occ
3=Standby
4=SetbackMode
8=SetupMode
no-units
no-units
317
No
unitStatus
Shows current heating/cooling status of the box:
1=CoolMode
2=VentMode
4=HeatMode
no-units
no-units
318
No
graphic_Stg2HeatSignal
Used for graphics. Analog variable heat signal.
no-units
no-units
323
Yes
maxDischargeTempStpt
Maximum temperature of duct discharge air temp
setpoint when dual max control is off.
110
°F
43
°C
327
No
graphic_Stg1HeatSignal
Used for graphics. Analog variable heat signal.
no-units
no-units
329
No
CO2_DemandVAV
Available for AHU outdoor air reset of the damper.
%
%
335
Yes
ductHeatPIDGain
PID gain tuned for duct heat.
3
no-units
3
no-units
355
Yes
perimeterHeatLockout
The outdoor air temperature that the perimeter
heat will be locked out.
65
°F
18
°C
361
No
perimeterHeatDemand
The calculated perimeter heat demand
%
%
372
Yes
AO14_LowAOValue
Custom low output voltage value for AO14 if
stg1OutType
set to 4
2
volts
2
volts
373
Yes
AO14_HiAOValue
Custom high output voltage value for AO14 if
stg1OutType
set to 4
10
volts
10
volts
388
Yes
AO15_LowAOValue
Custom low output voltage value for AO15 if
stg2OutType
set to 4
2
volts
2
volts
389
Yes
AO15_HiAOValue
Custom high output voltage value for AO15 if
stg2OutType
set to 4
10
volts
10
volts
408
Yes
heartbeatTimer
Time in minutes the digital heartbeat needs to
change to maintain communication status.
10
min
10
min