BBMD / NAT
BBMD
connects
BACnet IP
networks that are not on the same local network (see
Datagram Protocol (UDP) to send data packets. ASHRAE adopted BACnet/IP
in annex j of the 135- 1995 standard.
BACnet/IP communicates using four methods.
BACnet/IP to BACnet/IP (same subnet): Assuming that two devices know each other's IP
addresses and the UDP ports they are using, i.e., their respective B/IP addresses, there is nothing
that restricts them from communicating directly.
BACnet/IP to BACnet/IP (different subnet): The location of the two devices is already known by
the host and the message is routed to the device using switches and routers.
Broadcast (same subnet): This is a standard Who is/ I am message sent across a local subnet for
the BBMD to discover what the address are for the BACnet devices on the subnet.
Broadcast (different subnet): This is a standard Who is/ I am message sent across a local subnet
for the BBMD to discover what the address are for the BACnet devices on other subnets.
IP Broadcast Management Device (BBMD) on page 18 for details).
NAT connects sites where there is a
NAT
gateway between them.