Manual Energy Storage Inverter ESI-S
The ESI-Manager user interface 97
row and then from the dropdown menu, replace that harmonic order by any other
harmonic of choice.
−
Note: Above procedure is only to include (or exclude) any harmonic order in the
list. Further to that, the user must select specific harmonics by choosing Yes or
No from the other dropdown menu for the inverter to consider them for filtering
−
To set the curve value, the “curve” data entry window needs to be selected. As
soon the window is touched, the numeric keypad appears allowing the user to set
a desired curve level (in terms of Amp). Fractional values are not accepted and are
rounded off to the nearest integer. Once all the harmonics are programmed, the
harmonic selection table can be exit by pressing. The
button at the top right
corner.
7.9.2.1.3 Deselect all harmonics
For deselecting all harmonics of the main window at once go to
[/Welcome/Settings/Customer set./Main settings/Deselect all]
For deselecting all harmonics of the auxiliary window at once go to
[/Welcome/Settings/Customer set./Auxiliary settings/Deselect all]
This function allows for the customer to quickly deselect all harmonics in the main or the
auxiliary window. This may be useful e.g. when the commissioning engineer realizes that
the CTs have been installed wrong and an intervention is required to correct the problem.
7.9.2.1.4 Selecting the reactive power compensation and balancing options
The balancing feature is not available in single phase inverter.
The active inverter can perform different reactive power tasks based on CT’s
measurements including balancing, each of which require the appropriate setup.