Manual Energy Storage Inverter ESI-S
The ESI-Manager user interface 113
For commissioning the temperature probe(s), go to
[/Welcome/Settings/Commissioning/T Commissioning]
User can connect up to eight temperature probes in a daisy chain to the ESI-Manager.
Each probe needs to be commissioned as following procedures before it can be used.
Each probe has to be recognized one by one:
−
Connect the probe to the temperature probe input (one probe only)
−
Click on a row to assign a probe number
−
click on the “Start” button
−
The ESI-Manager recognize automatically the probe address
−
Restart the same procedure for each probe
When one of the probes has a problem, it can be cleared by selecting that row and
clicking the “Clear” button. A unique address will be assigned to each activated probe
after the recognition completes. This unique address is a set of eight groups of numbers
like:
142 85 0 25 12 1 12 156