146 Commissioning instructions
Manual Energy Storage Inverter ESI-S
−
For deselecting all harmonics of the auxiliary inverter settings at once go to
[/Welcome/Settings/Customer set./Auxiliary settings/Deselect all]
−
For deselecting the reactive power compensation option of the main inverter
settings disable the option ‘PFC type’ in
[/Welcome/Settings/Customer set./Main settings/Main PFC/Bal.]
−
For deselecting the load balancing option of the main inverter settings disable
the option ‘Balance load’ in
[/Welcome/Settings/Customer set./Main settings/Main PFC/Bal.]
−
For deselecting the reactive power compensation option of the auxiliary inverter
settings disable the option ‘PFC type’ in
[/Welcome/Settings/Customer set./Auxiliary settings/Aux. PFC/Bal.]
−
For deselecting the load balancing option of the auxiliary inverter settings
disable the option ‘Balance load’ in
[/Welcome/Settings/Customer set./Auxiliary settings/Aux. PFC/Bal.]
For more information on the main and auxiliary settings concept, refer to
Section 7.9.2.1
8.7 Step 6: Start the system
Fit the inverter top cover before starting the system.
The ESI-S contains a main contactor that is controlled by the inverter controller.
WARNING: Under no circumstances close the main contactor manually. Failure to
adhere to this guideline may result in physical danger and in inverter damage.
In order to start it with the ESI-Manager:
−
Press
repeatedly until the ‘Welcome’ screen is displayed
−
Highlight the inverter start/stop menu (‘ESI’ item in the list). In this menu, the
‘START’ indication should be present.
−
Press
. The inverter will ask confirmation and then it will start. The main
contactor should close within 30 seconds. One second after closing, the IGBTs
will start and the inverter will charge the DC capacitors in order to reach the
battery voltage. Once it reach it, the inverter will close the DC contactor and will
be connected to the battery without power flow.
−
The ‘START’ indication in the start/stop menu changes in a ‘STOP’ indication once
the inverter is running
Detailed information on the inverter start/stop menu can be found in
Section 7.7
Remarks: