Manual Energy Storage Inverter ESI-S
Electrical design and installation 65
Two connection approaches exist:
−
The first approach is to use one digital input for the start function and the second
digital input for the stop function.
shows the ESI-Manager setup for the
input considered and the resulting effect when applying voltage to this input.
Table 30: Inverter behavior as a function of the ESI-Manager settings for local start/stop
and using 2 digital inputs
ESI-Manager setup for
digital input
Vlow applied to digital
input
Vhigh applied to digital input
Edge ON
No effect
Inverter starts on rising edge
Edge OFF
No effect
Inverter stops on rising edge
Remark: Vlow = 0 Vdc, Vhigh = 15-24 Vdc
When using the Edge ON function the inverter can only be switched on by applying
voltage to the digital input considered. It is therefore recommended in that case to
configure and cable the second digital input as Edge OFF. Refer to
Section 7.9.2.4.2
guidelines on how to set up the digital inputs according to the function required.
The electrical requirements of the digital inputs are as discussed in
shows a cabling diagram for implementing a start function on the first digital input
and a stop function on the second digital input.
External
stop push
button
24 Vdc
external
supply
+
-
1
(a)
2
(a)
3
(a)
4
(a)
ESI-Manager
Digital input 1 (15-24Vdc)
Digital input 2 (15-24Vdc)
Remark:
(a)
Left hand terminal block when looking from rear, counting from top to bottom
External
start push
button
Figure 46: Cabling diagram for implementing start on digital input 1 and stop on digital input 2
−
The second approach is to use one digital input for both the start function and
the stop function. This leaves the other digital input available for the
implementation of other functions.
shows the ESI-Manager setup for the input considered and the resulting effect
when applying voltage to this input.