Modifications reserved
Page 9/26
7
Output characteristics
7.1
System output characteristics
DPA UPScale S2
AC power distribution system
TN-S, TN-C, TN-C-S, TT, 3ph
Output rated voltage
V
3 x 380/220 V or 3 x 400/230 V or 3 x 415/240 V
Output voltage stability
%
Static:
< +/- 1%
Dynamic (step load 0%-100% or 100%-0%)
< +/- 4%
Output voltage distortion
%
With linear load
< 1.5%
With nonlinear load (EN62040-3:2001)
< 3%
Output frequency
Hz
50 Hz or 60 Hz (selectable)
Output frequency tolerance
%
Synchronized with mains
< +/- 2%
(selectable for bypass operation)
or < +/- 4%
Free running
+/- 0.1%
Efficiency AC-AC
(at cosphi 1.0)
(tol/- 0.5%
applies on all figures)
%
Load
: 100%
75%
50%
25%
:
95.5
95.5
95
94.5
Eco-mode efficiency
at 100% load
%
98%
Permissible unbalanced load
(All three phases regulated
independently)
%
100%
Phase angle tolerance
(With 100% unbalanced load)
°
< 2°
Crest factor (load supported)
3:1
7.2
Module output characteristics
Module type
UPScale M10
UPScale M20
Output rated apparent power
(cosphi 0.8)
kVA
10
20
Output rated active power
(cosphi 1.0)
KW
10
20
Output nominal current (In)
at 230 VAC ph-N and cosphi
1.0
A
14.5
29
Overload capability on inverter
%
125% load
10 min.
150% load
60 sec.
Output short capability on
static bypass (RMS)
A
10 x In during 20 ms
Output short capability on
inverter (RMS)
A
3.0 x In during 40 ms
2.25 x In during 40 ms
(3.0 x In optional)
Static bypass transfer time:
inverter
bypass / bypass
inverter / in Eco-mode
ms
<1 / <5 / <6
Summary of Contents for DPA UPScale ST40
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...