6.
Simultaneously press both “ON/OFF” buttons to start-up UPS.
The LCD panel must display: The LED indicator will appear as shown below:
LED Indicator
Color
LINE 1
Green
LINE 2
Green
BYPASS
Green
INVERTER
OFF
BATTERY
Green
7.
Open maintenance bypass (IA1) by turning it to “OFF” position. The load is now supplied by
the static bypass.
8.
Transfer load to mains and inverter for testing using the COMMANDS submenu.
9.
Transfer load to inverter mode by using the COMMAND “LOAD TO INVERTER”. On theLCD:
“LOAD PROTECTED” will appear.
THE LOAD IS NOW PROTECTED BY THE DPA UPSCALE ST S2