Modifications reserved
Page 40/79
5.7.3
Single input feed (standard version)
5.7.3.1
Block diagram
Cable sections and fuse ratings recommended. Alternatively, local standards to be respected.
Fig 5.7.3.1-1: Single input feed block diagram
5.7.3.2
Cable sections
Frame type
Load
in kW
Input 3x400V/230V
Output 3x400V/230V @
cosphi 1.0
Battery
Fuse A
(Agl/CB)
Cable A (mm
2
)
(IEC 60950-1)
Max. Input Current
with battery charging [A]
Cable D (mm
2
)
(IEC 60950-1)
I nom
[A]
Fuse E
+ / N / -
(Agl/CB)
Cable E (mm
2
)
for CBAT UPScale 120
or 200 ONLY
+ / N / -
Com. Battery
Sep.
Battery
UPScale ST 40
40
3x80A
5x16
68 A
5x16
58 A
NOT ALLOWED
UPScale ST 60
60
3x125A
5x35
102 A
5x35
87 A
UPScale ST 80
80
3x160A
5x50
136 A
5x50
116 A
3x224A*1
3x95 *1
4x (3x10)
UPScale ST120
120
3x224A
4x95+1x50 (PE)
208 A
5x70
174 A
3x300A*1
3x150 *1
6x (3x10)
UPScale ST 200
200
3 x 350 A
5 x 185
333 A
5 x 185
290 A
3 x 450 *1
3 x (2 x 95)*1
5 x
(3x25)
*1 only valid for common battery use
Summary of Contents for DPA UPScale ST40
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...