![ABB DPA UPScale ST40 User Manual Download Page 69](http://html1.mh-extra.com/html/abb/dpa-upscale-st40/dpa-upscale-st40_user-manual_3448140069.webp)
Modifications reserved
Page 69/79
8.2.3
Output short capability 3 x In
This option increases the output short circuit capability of the DPA UPScale power module M20 to 3 x
In for a duration of 40ms.
Order Number
4NWP101746R0001
Output short capability 3 x In
8.3
Wiring
8.3.1
Halogen free cable
Halogen-free cabling is becoming relevant for the public sector (airports, rail/metro infrastructure, etc.)
to mitigate the risk of toxic and corrosive gas emissions during a fire or short-circuit fault.
DPA UPScale St S2 can be internally wired by using halogen-free cable.
Order Number
4NWP101680R0001
Kit HF cables Upscale ST40 S2
4NWP101704R0001
Kit HF cables Upscale ST60 S2
4NWP101701R0001
Kit HF cables Upscale ST80 S2
4NWP101702R0001
Kit HF cables Upscale ST120 S2
4NWP101703R0001
Kit HF cables Upscale ST200 S2
8.4
Control and monitoring
The Simple Network Management Protocol (SNMP) is a worldwide-standardized communication-
protocol. It is used to monitor any device in the network via simple control language. The UPS
management software provides its data in this SNMP format with its internal software agent. The
operating system you are using must support the SNMP protocol. ABB offers its software with SNMP
functionality for Novell, OS/2, all Windows operating systems running on Intel and ALPHA, DEC VMS
and Apple.
Two types of SNMP interfaces with identical functionality are available: an external SNMP adapter
(box) and an internal SNMP card. Both can manage a parallel system (N modules) and return either
global values - which are consistent for the whole parallel system - or specific values from the single
modules.
Fig 8.4-1: SNMP
UPS
Ethernet
9
External SNMP-Adapter
Internal SNMP-Card
Summary of Contents for DPA UPScale ST40
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...