Chapter 3 - Handling of Control Panel CDP 312
DCS 600 Operating Instructions
IV F
3 - 11
3.9 Uploading and Downloading of Parameters (UPLOAD/DOWNLOAD)
FUNC
CAUTION!
The drive must be in standstill condition with given
STOP command (controllers blocked, power section
disconnected from the network) when
UPLOAD/
DOWNLOAD
function is selected.
The upload and download function is operative for
groups 10…97
RAM
Factory
Actual
User 2
User 1
FPROM
Auto-
matically
99.11 =
Factory
Us
e
r1
Sa
v
e
Us
e
r1
Lo
ad
Us
e
r2
Sa
v
e
Us
e
r2
Lo
ad
Start
99.9 = Yes
'2:1/2$'
83/2$'
SDCS-CON-2
SDCS-AMC-DC
Only required for
changed unit-(type-)
dependent values:
[P 15.02] = 22
&RQWURO
3DQHO
CDP 312
RAM = Random Access Memory
FPROM = FLASH-PROM
RAM
FPROM
FPROM
'&6
UPLOAD
will copy all parameters, which are different to default,
from the
RAM
memory of the SDCS-AMC-DC board to the
FPROM
memory of the Control Panel CDP 312.
Before a
DOWNLOAD
is started the factory-set values (default
values) should be available within the
RAM
memory of the SDCS-
AMC-DC board. Factory-set values are always available in the
FPROM
memory of this board and they can be called by means of
APPLIC_RESTORE
parameter
99.09
with the exception of the
group 99. Parameter
99.11 APPLICATION MACRO
has to be set
to
FACTORY
.
The exceptional group has to be checked and if necessary,
changed by manual setting. Instead of this a saved default pa-
rameter set can be loaded by DRIVES WINDOW.
The
DOWNLOAD
will copy all values stored in the
FPROM
memory
of the CDP 312 to the
RAM
memory of the SDCS-AMC-DC board.
Note:
For reasons of safety the
DOWNLOAD
function will only
operate if “
LOCAL
mode” of the Control Panel CDP 312