Chapter 3 - Handling of Control Panel CDP 312
IV F
3 - 2
DCS 600 Operating Instructions
3.2 Start Mode
Note: The CDP 312 can be connected to the drive without discon-
necting the auxiliary power!
When the
CDP 312
is
connected and power is applied to the elec-
tronics, the display will show:
1. Name and Software version of the Control Panel; an increasing
number of points (row) in the lower line will show, that data
from the Software used with
DCS 600
are loaded. If this row
is repeated permanently, it will not be possible to load data as
(for example) there is no correct running of the Software or the
SDCS-AMC-DC board is missing.
-.::+8/6@
2. ID number and number of drives connected to the link.
3.8?7,/<
.-=
3. Afterwards the display will change over to the Actual Signal
Display Mode. Now the selected values are shown here.
4. If a fault or alarm is effective, the corresponding (signal) display
will appear after item 3.
The following message is displayed if the
CDP 312
is not able to
communicate with the drive:
0+?6>
89-977?83-+>398
89-977?83-+>398EbG
EbG
The CDP is not active for 10 s
The drive is not active for 10 s
No data set received for 2 s
Bus administrator is offline
•
The drive is not present on the link. This is the case if the drive
stops communicating.
•
The link does not operate because of a hardware malfunction or
a cabling fault.
Action: Disconnect the
CDP 312
and connect it again to the
drive. Hereby the
CDP 312
will be forced to the Start
Mode once again!