Chapter 2 - Start-Up Instructions
DCS 600 Operating Instructions
IV F
2 - 31
DCS 600 and Modbus PLUS
Hardware
DCS 600
SDCS-AMC-DC classic
board
NMBP-01
Software 1.3
Cable
length 0.2 ... 10 m
plastic optical fibre
Associated publications
DCS 600
Technical Data
3ADW000054R0301
ABB Lampertheim
Software Description
3ADW000076R0401
ABB Lampertheim
DC Converter Fieldbus
3ADW000097R0101
ABB Lampertheim
(not on database)
Database
GLOBAL\DEIND\DEIND051.NSF
Modbus
NMBP-01
3AFY58919802R0125RevB
ABB Helsinki
PLUS
Database
GLOBAL\FIDRI\FIDRI002.NSF
Software settings
DCS 600
Parameter
98.02
=
2 (FIELDBUS)
70.01
=
1
70.02
=
Optical power/cable length
(use default)
70.20
=
1
Default connected
Main control word
(data set 1/1)
parameters
Speed reference
(data set 1/2)
Main status word
(data set 2/1)
Motor speed
(data set 2/2)
Drive
Parameter
Fieldbus
Par. No.
Parameter Name
Select
51.01
1
MODULE TYPE
MODBUS PLUS
51.02
2
MODULE MODE
0
51.03
3
DRIVE NUMBER
2 to 64
51.04
4
GOOD MESSAGES
0 to 32767
51.05
5
BAD MESSAGES
0 to 32767
51.06
6
GLOBAL DATA OUT 1
1
51.07
7
GLOBAL DATA OUT 2
0 to 6
51.08
8
GLOBAL DATA OUT 3
0 to 6
51.09
9
GDATA IN 1STATION
1 to 64 PLC station No.
51.10
10
GDATA IN 1WORD
1
= Self-adjustment while switching on
To be continued!