Chapter 2 - Start-Up Instructions
DCS 600 Operating Instructions
IV F
2 - 27
DCS 600 and AC 80 Drive bus
Hardware
DCS 600
SDCS-AMC-DC
board
AC 80
Drive bus
Cable
length 0.2 ... 20 m
plastic optical fibre
Transmission speed
4Mb
Star configuration (NDBU95)
up to 12 drives - select Drive bus mode
Associated publications
DCS 600
Technical Data
3ADW000054R0301
ABB Lampertheim
Software Description
3ADW000076R0401
ABB Lampertheim
Database
GLOBAL\DEIND\DEIND051.NSF
AC 80
AC 80 User manual
3BFE 64116487
AC 80 Reference manual
3BFE 64021737
Data base
GLOBAL\FIDRI\FIDRI002.NSF
Software settings
DCS 600
Parameter
98.02
=
3 (ADVANT)
70.01
=
Drive Number
70.02
=
Optical power/cable length
(use default)
70.20
=
10
71.21
=
Star
Connected parameters
Main control word
(data set 10/1)
Speed reference
(data set 10/2)
Main status word
(data set 11/1)
Motor speed
(data set 11/2)
For additional p. see SW Descr. chap. ”Communication”
AC 80
Node Type
AC 80
DB element
DRB00
DRTYP1
=
AMC Classic for AMC DC
DRTYP1
=
NAMC 2 for AMC DC Drive Bus
PC element
ACSRX
DRNR
=
Drive number
EN
=
1
CNTRL
=
1
DS1
=
Data set number
WR
=
1
Maximum two data sets in one ACSRX block AMC DC
Example for switch-on sequence
Send to control word 7.01
0476H
(ON = 0; READY, if there is no failure)
0477H
(main contactor ON)
047FH
(RELEASE for speed and current control)
Note:
Before receiving the first dataset the drive sets the CH 0 alarm status