Step
Action
above the fan shelf.
4.
Attach de
-
energized DC cabling (typically 14 AWG) as shown here. Use ring lugs or alternate per local practice.
Fuse externally at 5 Amps. Note: Returns for the A and B feeds are shared on the
-
48Vdc RTN. The lowest posi-
tion on the terminal block is to provide frame ground for the fan shelf. Power feeds should be derived from a fuse
or breaker panel using discrete cabling which is independent from the converter shelf.
Figure 18 DC Cabling Fan Trays in CPS3200U Systems
Included Communication Wire set
Fan Shelf
Converter Shelf
(Door removed for visibility)