Step
Action
1.
Is accessibility to the circuit throughout the network consistent with A3 requirements?
2
Is the 5
-
pin protector marked as a special circuit?
3.
Does the 5
-
pin protector protect each pair to a level corresponding to a CommScope 3C*EW Gas tube primary pro-
tector? This protector has a voltage breakdown range of 265
-
465 Volts and an impulse spark over range of <265
-
700 Volts. Protectors with a lower voltage breakdown rating will be problematic.
7. Inspect the Network
-
Check and Mark Wiring Compliance
The CP/
-
190V system is classified as an A3 circuit tested according to GR
-
1089
-
CORE Issue
6. As such, each location in the network where the output is available to be touched must be
protected and marked as an A3 voltage.
Voltage Class
General public
Employees
Craftsperson's
A 1
Restricted access
Exposed
Exposed
A 3
Inaccessible
Inaccessible
Restricted access
( Exceptions )
Table 7
-
1 accessibility to continuous class –A voltage
Summary of Contents for CPS3200U
Page 1: ...Page 1 2021 ABB All rights reserved PRODUCT MANUAL ...
Page 12: ...Page 12 2021 ABB All rights reserved This page intentionally left blank ...
Page 17: ...Page 17 2021 ABB All rights reserved Figure 2 Capacitance Safety Limits ...
Page 20: ...Page 20 2021 ABB All rights reserved This page intentionally left blank ...
Page 22: ...Page 22 2021 ABB All rights reserved This page intentionally left blank ...
Page 33: ...Page 33 2021 ABB All rights reserved Step Action 2 ...
Page 34: ...Page 34 2021 ABB All rights reserved Step Action Slide the filter in to the filter bracket 4 ...
Page 43: ...Page 43 2021 ABB All rights reserved Step Action 14 ...
Page 48: ...Page 48 2021 ABB All rights reserved ...
Page 51: ...Page 51 2021 ABB All rights reserved 10 Maintenance ...
Page 52: ...Page 52 2021 ABB All rights reserved This page intentionally left blank ...
Page 62: ...Page 62 2021 ABB All rights reserved This page intentionally left blank ...