On the Interface board are located two LED’s:
Green LED showing the status of the Interface:
- Fast Blinking: 2 times/sec = Interface is Master (1
st
Cabinet of a parallel System)
- Slow Blinking: 1 times/sec = Interface is Slave ( 2
nd
,.. 5
th
cabinet of a //- System)
Red LED
Board Alarm (indicates a possible replacement of the board)
On the Master board the following ports are active:
The Input ports (X1)
The Output port (X2, X3, X4)
On the Salve boards the following parts are active.
The Output ports X3/6 … X3/10 and X4/1 …X4/10 (Means Alarm . Module 1 , 2, 3 ,4, 5)
All other input or output ports on the Slave boards are not activated.
3.1.3 JD11 / RS232 Computer Interface
The
Computer Interface JD11
(4) located on the distribution part is an intelligent RS 232 serial port that allows
the UPS system to be connected to a computer. The connector JD11 is a standard D-Type, 9-pin, female.
When installed the
Computer Interface
, the optional WAVEMON software allows the computer to monitor the
mains voltage and the UPS system status continuously.
In the event of any changes the computer terminal will display a message.
(For details see our optional Monitoring Package:
WAVEMON
)
.
3.1.4 JD12 / RS232 Interface for Multidrop
The
Computer Interface JD12
(5) located on the distribution part is an intelligent RS232 serial port that allows to
get from several UPS cabinets which are connected in parallel the complete system information by using the
Multidrop connection kit. (For details see user manual Multidrop kit). The connector JD12 is a standard D-Type, 9-
pin, male.
3.1.5 USB/2 Computer Interface
The
Computer Interface USB
(6) located on the distribution part and is in parallel with the intelligent
RS 232 serial port
JD11
.
When installed the
USB Computer Interface
trough, the optional WAVEMON software allows the computer to
monitor the mains voltage and the UPS system status continuously.
In the event of any changes the computer terminal will display a message.
(For details see our optional Monitoring Package:
WAVEMON
)
.
Fig. 3. Example : Distribution Interfaces
1
X1-X4 Customer interface on Phoenix Terminals:
X1 Customer Inputs
X2…X4 = Outputs Potential free contacts
2
SW1-9
Multi-Cabinet Configuration Switch
3
JD8
Parallel BUS connector
ONLY For paralleling cabinets use optional adapter:
JD5
Parallel BUS - Input Connector
JD6
Parallel BUS - Output Connector
4
JD11
RS232 / Sub D9/ female, PC interface
5
JD12
RS232/ Sub D9 / male for Multidrop ONLY
6 USB
PC
Interface
7
SNMP
Slot for optional SNMP card ONLY