Section-1
04-3008_S1_ABB_OPMCPDPA-S2_GB_121202
Page 9/22 ABB
Printed in Switzerland – Modifications reserved
1.3.2 Conceptpower DPA
TM
S2 basic system configuration
The UPS system is housed in single freestanding cabinets. The cabinets line up and match in style and colour, and
have safety shields behind the doors for hazardous voltage protection.
The following basic UPS systems configuration are available:
Fig. 1)
Fig. 2)
Fig. 3)
UPS Frame
Type
Module
no.
Packed
Weight with
DPA 30 w/o
Batt. in kg
Packed
Weight with
DPA 40 w/o
Batt. in kg
Packed
Weight with
DPA 50 w/o
Batt. in kg
Packed
Dimension mm
Unpacked Weight
with DPA 30 w/o
Batt. in kg
Unpacked
Weight with
DPA 40 w/o
Batt. in kg
Unpacked
Weight with
DPA 50 w/o
Batt. in kg
Unpacked
Dimension mm
Module
43.1 45.3 46.8
WxHxD
43.1 45.3
46.8
WxHxD
Fig. 1
CLASSIC-
DPA-50
1
328 330 332
890x1800x920
305 307
309
730x1650x800
Fig. 2
TRIPLE-
DPA-150
1
307 309 311
890x2120x920
282 284
286
730x1975x800
2
350 355 358
890x2120x920
325 330
333
730x1975x800
3
393 400 404
890x2120x920
368 375
379
730x1975x800
Fig. 3
UPGRADE-
DPA-250
1
273 275 277
890x2120x920
248 250
252
730x1975x800
2
316 321 324
890x2120x920
291 296
299
730x1975x800
3
359 366 370
890x2120x920
334 341
345
730x1975x800
4
402 411 417
890x2120x920
377 386
392
730x1975x800
5
446 457 464
890x2120x920
421 432
439
730x1975x800
1.3.3 Quality Standards and ups classification code
The Conceptpower DPA
TM
S2 will provide your critical equipment with a steady and reliable power supply for many
years.
The unique and modular UPS Conceptpower DPA
TM
S2 belongs to the newest generation of midrange 3phase
UPS-Systems. High reliability, low operating cost and excellent electrical performance are only some of the
highlights of this innovative UPS solution.
The criteria and methods implemented for the design and manufacture correspond to the most stringent quality
standards.
The manufacturer is certified successfully in every areas according to the model of the International Standard
ISO9001/EN 29001. The Certification of UPS with the operating performance according to the Norm
IEC 62 040-3 and VDE 0558 Part 530 is accomplished.
With it the UPS has the
Classification Code VFl-SS-111.
Product
Standards
Standards
Safety
IEC/EN 62040-1
IEC/EN 60950-1
Electromagnetic Compatibility
EMC
IEC/EN 62040-2
IEC/EN 61000-6-2
IEC/EN 61000-6-4
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
Performance IEC/EN
62040-3