1.5.2.2 Positioning
UPS designed for location in a restricted access location only!
UPS :
A minimum 20 cm rear space from the UPS to an obstruction is recommended for proper cooling as the air
enters at bottom/front and exits at unit rear (see Fig. 1. and 2.)
External Battery :
It’s recommended to install external battery cabinet(s) next to the UPS unit. The external battery
can be placed on either side of the UPS unit, but it is recommended to install on left hand side.
Check before the installation that the battery voltage values in the type plate of the UPS and external battery
cabinets are the same.
WARNING!
THE UPS CONTAINS HIGH DC VOLTAGES. A QUALIFIED PERSON MUST DO
THE CONNECTIONS BETWEEN THE UPS AND THE EXTERNAL BATTERY
CABINET(S). THE BATTERY CABINET IS CONNECTED ELECTRICALLY IN
PARALLEL WITH THE INTERNAL BATTERIES OF THE UPS.
WARNING!
IF AVAILABLE, THE INTERNAL BATTERY HAS TO BE DISCONNECTED
FIRST BECAUSE THE EXTERNAL
BATTERY TERMINALS ARE HAZARDOUS DUE TO THE PARALLEL
BATTERY STRING.
Battery Racks:
External battery racks shall be sized to take the voltage drop in the cable into account. To obtain
support and help contact the local office or agent authorized by the manufacturer.
Clearances X Y
Minimum 200mm
900
mm
UPS
Frames
X
Battery
Cabinet
UPS
Frames
X
Figure 1: UPS space recommendation
Figure 2 : UPS + Battery space recommendation
Open Doors
Y
Open
Doors
Y