Section-2
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202
Page 11/16 ABB
Printed in Switzerland – Modifications reserved
2.3 BATTERY
CONNECTIONS
2.3.1 INTERNAL BATTERY MODULES
2.3.1.1
Internal Battery Modules CLASSIC DPA-50
In
Conceptpower DPA
TM
S2
CLASSIC DPA-50 FRAME
there is space for up to 280 x 9Ah internal batteries.
In the drawing below different Battery and System configurations are shown. The batteries may be used as
separate batches for each UPS-Module or they can be used as common batteries for all tree UPS-Modules.
NOTE
: For UPS-Systems DPA 30kVA and DPA 50kVA it is allowed to use 40-50 (only even numbers) of 12V-
battery blocks.
NOTE
: Set-up the correct number of battery blocks on Control Panel (Menu: Service-Set-Up).
CONCEPTPOWER CLASSIC DPA-50
(5x50)x7Ah
(4x50)x7Ah
(3x40)x7Ah
Other combination possible : refer to Section 10
2x5x7Ah
2x5x7Ah
2x5x7Ah
1
2
3
4
A
B
C
10x7Ah
10x7Ah
10x7Ah
10x7Ah
5
10x7Ah
10x7Ah
10x7Ah
10x7Ah
6
10x7Ah
10x7Ah
10x7Ah
10x7Ah
F1
7
D
UPS 1
2x5x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
2x5x7Ah
2x5x7Ah
2x5x7Ah
1
2
3
4
A
B
C
10x7Ah
10x7Ah
10x7Ah
10x7Ah
5
10x7Ah
10x7Ah
10x7Ah
10x7Ah
6
10x7Ah
10x7Ah
10x7Ah
10x7Ah
F1
7
D
UPS 1
2x5x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
2x5x7Ah
DPA CLASSIC 50 frame
DPA CLASSIC 50 frame
DPA CLASSIC 50 frame