Section-2
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202
Page 8/16 ABB
Printed in Switzerland – Modifications reserved
14 15 16
1
2
3
4
5
6
7
8
9 10 11 12
14 15 16
19 20 21
13
1
X1-X4 Customer interface on Phoenix Terminals:
X1 Customer Inputs
X2…X4 = Potential free contacts (detail see Section 3 / 1.2 )
2
SW1-9
Multi-Cabinet Configuration Switch (see section 4)
3
JD8
Parallel BUS connector
ONLY For paralleling cabinets use optional adapter:
JD5
Parallel BUS - Input Connector
JD6
Parallel BUS - Output Connector
4
JD11
RS232 / Sub D9/ female, PC interface
5
JD12
RS232/ Sub D9 / male for Multidrop ONLY
6 USB PC
Interface
7
SNMP
Slot for optional SNMP card ONLY
8
Modem
Slot for optional Modem/Ethernet card ONLY
9
9 Battery te / N / - for separate bat.
16/25 mm2
9*
3 Battery terminal for common battery
M10 + PE 1x M10
10
Input Bypass terminal for Dual Input feed
3xM10
11
Input Rectifier terminal for Single feed
4xM10
12
Output Load terminal
4xM10
13 IA1
Maintenance
Bypass
14
IA2-1
Parallel Isolator UPS-Module 1
15
IA2-2
Parallel Isolator UPS-Module 2
16
IA2-3
Parallel Isolator UPS-Module 3
19
F4 Battery Fuse Holder Module 1
14x51/ 50A Fast Acting
20
F5 Battery Fuse Holder Module 2
14x51/ 50A Fast Acting
21
F5 Battery Fuse Holder Module 3
14x51/ 50A Fast Acting